Index  88 

U

 

updating the firmware   45, 55 

UPS alarms   65 
UPS Alarms table   24 

UPS Data Log screen   27 

UPS Status table   23 

UPS, about   24 

V

 

views   19 

W

 

web interface requirements   9 

web interface, overview   16 

web interface, using and navigating   19 
 

Summary of Contents for UPS Network Module

Page 1: ... information for the HP UPS Network Module This document is for the person who installs and maintains power products HP assumes you are qualified in the servicing of high voltage equipment and trained in recognizing hazards in products with hazardous energy levels Part Number 637918 001 June 2011 Edition 1 ...

Page 2: ...al or editorial errors or omissions contained herein Confidential computer software Valid license from HP required for possession use or copying Consistent with FAR 12 211 and 12 212 Commercial Computer Software Computer Software Documentation and Technical Data for Commercial Items are licensed to the U S Government under vendor s standard commercial license Microsoft and Windows are U S register...

Page 3: ...ule network settings 15 HP UPS Network Module web interface 16 HP UPS Network Module web interface overview 16 Accessing the web interface 16 Browser security alert 17 Establishing a secure session for Internet Explorer 17 Establishing a secure session for Mozilla 18 Establishing a secure session for Firefox 18 Establishing a secure session for Google Chrome 19 Navigating the web interface 19 View...

Page 4: ...uration 56 Configuring the firewall on Windows 56 Security considerations 64 Security considerations overview 64 Alert messages 65 UPS alarms 65 SNMP trap codes 69 SNMP trap codes 69 Specifications 72 Technical characteristics 72 Default parameters 73 Troubleshooting 75 Client communication failure with HP UPS Network Module in a VMware operating system 75 Client server is not restarting 75 Client...

Page 5: ...d with the FCC logo United States only 79 Modifications 79 Canadian notice Avis Canadien 79 European Union regulatory notice 80 Disposal of waste equipment by users in private households in the European Union 80 Chinese notice 81 Japanese notice 81 Korean notice 81 BSMI notice 82 Acronyms and abbreviations 83 Index 86 ...

Page 6: ... minislot card that requires UPSs equipped with a minislot The UPS Network Module Monitors the status performs UPS diagnostics and transmits periodic reports Manages independent UPS load segments to provide separate power control of connected equipment Prioritizes the timing of equipment shutdown and reboots connected equipment by load segment Delays restart by load segment after a power outage to...

Page 7: ...is powered by the UPS and any machine that the UPS Network Module uses to initiate a shutdown command For more information see the HP Power Protector User Guide on the HP website http www hp com go rackandpower You can also use a third party SNMP manager to monitor the power protection For more information see SNMP monitoring on page 51 Supported hardware configurations The UPS Network Module can ...

Page 8: ...PPP Client over the network Green Power connection Red Communication path Configuration B This figure illustrates one or more HPPP Clients are redundantly powered by two UPSs and communicate with two UPS Network Modules over the network to begin a graceful shutdown in the event of a power failure or other configured shutdown events NOTE Up to 35 HPPP Clients can be managed by one HP UPS Network Mo...

Page 9: ...k Green Power connection Red Communication path Web interface requirements The following table lists the minimum requirements necessary to operate the UPS Network Module web interface Software Browser Internet Explorer Windows Internet Explorer 7 Windows Internet Explorer 8 Windows Internet Explorer 9 Mozilla HP UX Mozilla 1 4 x Firefox Linux Firefox 3 5 x native to Linux version Windows Firefox 3...

Page 10: ...ngs using the Shutdown Parameters screen on page 35 4 optional Configure additional settings using the menus under Settings on page 30 5 Install and configure the HPPP Client on all servers to be protected by the UPS After all Clients are configured at the servers they are automatically added by the UPS Network Module and appear on the Notified Applications screen on page 40 For more information s...

Page 11: ...cted Flashing green UPS Network Module connected to the network and sending or receiving data 3 Network Speed LED Off Port operating at 10 Mb s Solid orange Port operating at 100 Mb s 4 Settings AUX connector Configuration port 5 UPS Data LED Off UPS Network Module starting Solid green UPS Network Module communicating with UPS Flashing green Normal operation communication link established 6 Config...

Page 12: ...utine maintenance and service of this product must be performed by individuals who are knowledgeable about the procedures precautions and hazards associated with AC power products Required tools No 2 Phillips screwdriver Installing the UPS Network Module NOTE It is not necessary to power down the UPS before installing the UPS Network Module 1 Remove the two screws securing the UPS option slot cove...

Page 13: ... minutes 4 Secure the UPS Network Module using the two screws you removed in step 1 Connecting the network cable Connect a standard Ethernet cable between the network connector on the UPS Network Module and a network jack This connection is used to access the UPS Network Module remotely through the web interface The UPS Network Module also uses the network connection to communicate to the configur...

Page 14: ...osoft Windows and is used in this section as an example for setting up a terminal emulation session If you are using another utility the steps might be different 1 Be sure that the UPS is powered on 2 On the host computer click Start and select Programs Accessories Communications HyperTerminal The Connection Description window appears 3 Enter a description select an icon for the connection and the...

Page 15: ...ith a DHCP server the network settings are automatically assigned To view the settings a On the Main menu enter 2 to display the Network Configuration submenu b Enter 1 to view the network settings c Record the IP address d Enter 0 to return to the Main menu e Enter 0 to exit the Configuration Menu The UPS Network Module is operational NOTE You can configure the DHCP server to permanently assign t...

Page 16: ... configured using the HP UPS Network Module Configuration Menu on page 46 Accessing the web interface CAUTION It is highly recommended that browser access to the UPS Network Module is isolated from outside access using a firewall or isolated network 1 On a network computer launch a supported browser The browser window appears 2 In the URL field enter http xxx xxx xxx xxx or https xxx xxx xxx xxx w...

Page 17: ...ty certificate which identifies the UPS Network Module If your browser displays a security alert when browsing to the UPS Network Module it can be for one of several reasons The certificate is untrusted meaning it was signed by a certifying authority that is unknown to your browser The certificate has expired or is not yet valid This condition can occur if you issue your own certificate and it has...

Page 18: ...can manually import the file into the browser by clicking Tools Internet Options Content Certificates Import Establishing a secure session for Mozilla The first time you browse to the UPS Network Module the Secure Session screen appears To ensure a secure connection verify that you are browsing to the desired UPS Network Module 1 Click Examine Certificate 2 Verify that the name in the Issued To fi...

Page 19: ...work Module through a secure connection The certificate appears with a warning 2 Click Proceed anyway and then login to the UPS Network Module web interface Navigating the web interface The web interface is divided into two frames Menu tree Contains a list of menu options on the left side of the screen Main frame Contains the various interface screens based on the menu option selected in the left ...

Page 20: ...UPS alarms Gray UPS communication loss UPS name The name of the UPS The UPS name is the generic name of the UPS model and this name displays throughout the interface UPS location The location of the UPS The UPS location can be modified on the System Settings screen on page 30 UPS graphical representation A graphical representation of the UPS model UPS operating mode diagram An animated graphical r...

Page 21: ...PS output current o AC Output Frequency The UPS output frequency o Load Level The percentage of load at the UPS output o Apparent Power The UPS apparent power o Active Power The UPS active power The following table describes the possible UPS operating mode diagrams Diagram UPS operating mode UPS with automatic bypass UPS without automatic bypass The following table describes the possible diagram e...

Page 22: ...battery test result Battery Output Flow Yellow AC to DC converter powered by battery Gray AC to DC converter not powered by battery DC to AC Converter Input Flow Yellow Energy flow present Gray No energy flow DC to AC Converter Green Powered Gray Not powered Red Internal failure DC to AC Converter Output Yellow Energy flow present Gray No energy flow AC Bypass Input Green In tolerance Red Out of t...

Page 23: ...le The UPS Status table displays the following basic information about power and output Power source Indicates whether the UPS is on utility power or running on the UPS battery Output load level The power percentage used at the UPS output Output Indicates whether the individual UPS outputs are protected o Entire UPS Indicates whether the UPS is powered on o Load segment 1 and Load segment 2 Indica...

Page 24: ...The About your UPS table displays the following hardware and firmware information for the UPS and the UPS Network Module UPS o UPS Name The name of the UPS o UPS Part Number The part number for the UPS o UPS Serial Number The serial number for the UPS o UPS Firmware Revision The firmware version for the UPS o Communication Board Firmware Revision The firmware version for the UPS internal communica...

Page 25: ...on Only users with administrator privileges can save command parameters and execute commands To configure a command 1 Select the command you want to run in the Control pull down menu Configured commands will not initiate until you click Execute o Safe power down A shutdown sequence for the load segment is launched immediately Connected equipment powers off and then the load segment powers off o Sa...

Page 26: ...uence initiates 4 Configure the On Delay time for power on commands Enter the number of seconds that should elapse between the time you execute the command and the restart sequence initiates 5 Click Save to save the Off Delay Toggle Delay and On Delay parameters 6 Click Execute to initiate the configured commands Click Help to view online help Schedule Shutdown screen Click Schedule Shutdown in th...

Page 27: ...lick Save Click Help to view online help Logs Menu options listed under Logs include UPS Data Log UPS Data Log screen on page 27 Event Log Event Log screen on page 28 System Log System Log screen on page 29 UPS Data Log screen Click UPS Data Log in the menu tree to display the UPS Data Log screen This screen displays a log of UPS data collected by the UPS Network Module The frequency at which data...

Page 28: ...s the maximum of 435 entries new entries overwrite the oldest entries in the log On the screen Click Save Log to download the log file csv to your computer Click Clear Log to clear the log files Only users with administrator privileges can clear logs Click Help to view online help Event Log screen Click Event Log in the menu tree to display the Event Log screen This screen displays a log of the ev...

Page 29: ...stem Log screen Click System Log in the menu tree to display the System Log screen This screen displays a log of the events that have occurred on the UPS Network Module such as a communication failure or system shutdown The following information is displayed for each event Date The date at which the event occurred Time The time at which the event occurred Event Description A description of the eve...

Page 30: ...ail Notification Email Notification screen on page 42 Firmware Upload Firmware Upload screen on page 45 System Settings screen Click System in the menu tree to display the System Settings screen This screen allows an administrator to enter contact information reset communication and restore factory default settings on the UPS Network Module To enter the system information 1 Enter the name of the p...

Page 31: ...is action is required to enable any changes made on the Network Settings screen on page 32 To restore all UPS Network Module parameters to the default configuration click Factory Reset The UPS Network Module communication will be lost To maintain communication select the Keep TCP IP parameters checkbox and then click Factory Reset The configured IP address subnet mask gateway and BOOTP DHCP parame...

Page 32: ...re protected by a user name and password and are only accessible in SSL Access to the web interface occurs through HTTPS The connections to the UPS Network Module remain in standard mode secure TCP 5 Click Save Click Help to view online help Network Settings screen Click Network in the menu tree to display the Network Settings screen This screen allows an administrator to configure network setting...

Page 33: ...nable or disable IPv6 respectively The local IP address of the UPS Network Module is built from the MAC address and appears in the IPv6 Local Address field when IPv6 is enabled 4 If IPv6 is enabled select the IPv6 Auto Config Enabled checkbox to have the IPv6 router build the IPv6 Address 1 Prefix length and IPv6 Address 2 The IPv6 Gateway field is empty and cannot be edited or Clear the IPv6 Auto...

Page 34: ...d 3 Enter the time hh mm ss in the Time field 4 Click Save To synchronize the date and time with HPPP Client NOTE Verify that the HPPP Client is configured with the correct date and time because the UPS Network Module uses the time from the first Client that responds 1 Select the Accept automatic update from HP Power Protector radio button 2 Click Save To synchronize the date time with an NTP serv...

Page 35: ...ons are 30 minutes and 1 hour 5 Click Save to connect to the NTP server and set the date and time The UPS Network Module uses the NTP protocol UDP 123 port The firewall must be set to transmit queries outside the network No error message is generated if connection with the NTP server fails The UPS Network Module attempts to connect to the NTP server every 10 seconds until a connection is made Clic...

Page 36: ...ion 1 Battery capacity 2 Time 3 Utility failure 4 Shutdown initiated 5 Load segment powered down 6 Low battery 7 Battery depleted 8 Operating system shutdown time 9 Remaining backup time under ii In the Shutdown initiated after field individual load segments enter the number of seconds after the power fails that the UPS Network Module should wait before starting to shut down the load segment 0 to ...

Page 37: ...after time iii In the Shutdown initiated if battery capacity under field individual load segments enter the minimum amount of battery life that can remain before the load segment shutdown sequence starts 0 to 100 20 by default The UPS Network Module initiates a load segment shutdown when the remaining battery life reaches the specified percentage NOTE This parameter can initiate the shutdown seque...

Page 38: ... Battery triggers is reached the shutdown sequence starts for that load segment or for the entire UPS When the OS Shutdown value is reached the shut down cannot be reversed even if utility power is restored c Enter the Restart values When utility power is restored all Restart settings are evaluated and the first trigger that is reached initiates the restart sequence IMPORTANT Carefully plan the re...

Page 39: ...ion supported by the UPS Network Module from the Version pull down menu Available options are Disabled V1 V3 and V1 and V3 2 Configure the SNMP V1 settings a Enter the SNMP Community Read Only string The UPS Network Module and the Clients must share the same community name to communicate b Select or clear the SNMP Write Enabled checkbox to enable or disable the SNMP write function c If the SNMP wr...

Page 40: ...Write Password to specify a new password for the Read Write User The password can be between 8 and 24 alphanumeric characters and the _ symbols g Enter a user name to include in SNMPV3 notification in the Notification Username field This field must also be defined in the applications that receive the notifications The user name can be between 8 and 24 alphanumeric characters and the _ symbols 4 Cl...

Page 41: ... Connection or Communication Loss To add a trap receiver 1 Click Add Trap Receiver 2 Configure the settings for the new application on the Trap Receivers Settings screen on page 42 To modify a trap receiver 1 Select the checkbox for the application you want to modify To select all applications click All 2 Click Modify Trap Receiver 3 Modify the settings for the application on the Trap Receivers Se...

Page 42: ... the name to for easy monitoring 2 Enter the host name or the IP address of the management server on which the application is running in the Hostname or IP address field 3 Select the SNMP version from the Protocol pull down menu 4 If you selected SNMP V1 enter the community string in the Trap Community field 5 Select the checkbox for the appropriate MIB o HP MIB cpqpower mib The HP Power MIB o IET...

Page 43: ...d in csv format 3 To send periodic email reports with log file attachments to the recipient a Enter the interval in days between email report transmissions b Select the time of the day when email reports are generated and transmitted from the pull down menu c Select the date of the month the next email report should be generated and transmitted After this date the screen indicates the date and tim...

Page 44: ...rmat of email messages initiated by the UPS Network Module The email message format applies to all recipients To customize email messages 1 Enter the address for the source of email messages in the Sender field The sender address can contain up to 59 characters The default value is ups domain com Depending on your SMTP server configuration an existing domain might be required with the user belongi...

Page 45: ...ary depending on the cellular service provider Contact your cellular service provider for mail to SMS gateway settings Click Help to view online help Firmware Upload screen Click Firmware Upload in the menu tree to display the Firmware Upload screen This screen allows an administrator to upgrade the UPS Network Module firmware During the upgrade process the UPS Network Module does not monitor the ...

Page 46: ...screen running on the host computer 1 Press any key The initialization process completes and you are prompted to enter the password 2 At the prompt enter admin The HP UPS Network Module Configuration Menu appears Navigating the menus After you have successfully initiated a terminal emulation session the UPS Network Module Configuration Menu appears Open a submenu by entering the corresponding opti...

Page 47: ...ubmenu Description 1 Hardware Reset Restarts the electrical power supply for the UPS Network Module 2 Restart Application Restarts the UPS Network Module application 0 Exit Returns to the previous menu Network Configuration submenu Option number Submenu Description 1 Read Network Settings Enables you to view IPv4 and IPv6 network settings for the UPS Network Module 2 Modify Network Settings Enable...

Page 48: ...odule can send event based traps to HP SIM that include a URL in the trap This functionality enables administrators to easily launch the web interface of the module in context For example if the UPS Network Module detects an alarm condition the module can send a trap to HP SIM with an attached hyperlink that routes users directly to the web interface for the attached UPS Conveniently launch the UP...

Page 49: ... additionalwsdisc txt file located in the same directory Example ADDITIONALWSDISC PROPS file with UPS Network Module entry Additional Web Server Discovery Properties NOTE See additionalWsDisc_README txt for a description of entries in this file and how to add or remove additional web server ports used for discovery and identification The following are actual web server ports enabled by default To ...

Page 50: ...A new file named cpqpower cfg is created 3 Register the new MIB by entering mxmib a cpqpower cfg from the HP Systems Insight Manager mibs command line 4 Enter HP Systems Insight Manager mibs mxmib at the command line and verify that the new MIB is listed NOTE For more information on uploading and registering a MIB in HP SIM refer to the HP Systems Insight Manager Technical Reference Guide located ...

Page 51: ... MIB and the HP Power MIB CPQPOWER MIB To query SNMP data you do not need to add SNMP Mangers to the Notified Application page In the third party SNMP manager configure the IP address of the UPS Network Module select SNMP V1 or V1 V3 and then compile either CPQPOWER MIB or UPS MIB RFC1628 to be monitored by the SNMP manager The HP Power MIB CPQPOWER MIB can be downloaded from the HP website http w...

Page 52: ...atically replaced by the longest OST when the Client is connected The updated value is displayed on the Shutdown Parameters screen for the UPS Network Module After the operating system shutdown begins the shutdown process cannot be canceled even if utility power is restored For load shedding each Client is shutdown based on its own delay settings This increases the backup time for the remaining Cl...

Page 53: ...ment 1 7 Load segment 1 8 Client 3 on load segment 2 9 Client 4 on load segment 2 10 UPS Network Module setting for load segment 2 11 Load segment 2 12 UPS On utility On battery SIA Operating system shutdown time OST t1 Utility failure UPS is on battery and all servers are powered as usual t2 Shutdown process initiated Shutdown scripts run applications close and the operating system shuts down t3 ...

Page 54: ...odule starts the shutdown process first Client 4 is forced to start its OST at the same time c UPS Network Module The UPS Network Module waits until t2 to initiate the shutdown sequence for load segment 2 and the other Clients Load segment 2 powers down at a new t3 which is the same as the longest Client OST 3 UPS Between the two OST of UPS Network Module on load segment 1 and load segment 2 the U...

Page 55: ...efault directory 4 Be sure that you have connected the configuration cable Connecting the configuration cable on page 14 to the UPS Network Module and the host computer 5 Launch a terminal emulation program such as HyperTerminal Launching a terminal emulation program on page 14 The following menu appears HP NETWORK MANAGEMENT CARD BOOTLOADER VERSION 1 1 RAM autotest in progress RAM autotest SUCCES...

Page 56: ...installed from using the following four ports to communicate with the UPS Network Module 4679 UDP Client 4680 UDP Client 5000 TCP Alarms 5001 TCP Alarms To configure the Windows XP with Service Pack 2 Firewall to make an exception for ports 4679 4680 5000 and 5001 1 Click Start select Control Panel and then double click Network Connections The Network Connections screen appears 2 Right click the n...

Page 57: ...lick the Advanced tab 4 In the Windows Firewall box click Settings The Windows Firewall screen appears 5 On the General tab verify that the Windows Firewall is enabled On and that the Don t allow exceptions checkbox is not checked ...

Page 58: ...Firewall configuration 58 6 Click OK 7 On the network Properties screen click the Exceptions tab 8 Be sure that the File and Printer Sharing check box is selected ...

Page 59: ...to allow communication through ports 4679 4680 5000 and 5001 The Add a Port screen appears 10 Enter a name for the HPPP Client port in the Name field 11 Enter 4679 4680 5000 or 5001 in the port number field 12 Select the appropriate radio button ...

Page 60: ...Firewall configuration 60 13 Click Change scope to add more security to the port exception ...

Page 61: ...Firewall configuration 61 The Change Scope screen appears 14 Select the Custom list radio button and then add the IP addresses that are allowed to communicate through the specified port ...

Page 62: ...Port screen click OK to finish adding the exception port The Windows Firewall screen displays the newly added HPPP Client port 17 Click OK NOTE Software that helps to protect your computer and blocks access on the network such as Windows Defender or firewalls needs to be reconfigured ...

Page 63: ...Firewall configuration 63 ...

Page 64: ...ich the UPS Network Module operates Remote access to the UPS Network Module requires a user account Logging in requires the use of a user name and password which should be kept properly secured Each account can be given different access levels providing different capabilities Ensure that the appropriate access level is granted to users Browsing to the UPS Network Module can be done using SSL which...

Page 65: ...Battery Discharged Cleared UPS Battery Disconnected UPS Battery Disconnected Cleared UPS Battery Low UPS Battery Low Cleared UPS Battery Over Voltage UPS Battery Over Voltage Cleared UPS Battery Test Failure UPS Battery Test Failure Cleared UPS Bypass AC Phase Out of Range UPS Bypass AC Phase Out of Range Cleared UPS Bypass Frequency Out Of Range UPS Bypass Frequency Out Of Range Cleared UPS Bypas...

Page 66: ...resent Cleared UPS Input AC Over Voltage UPS Input AC Over Voltage Cleared UPS Input AC Under Voltage UPS Input AC Under Voltage Cleared UPS Input Frequency Out Of Range UPS Input Frequency Out Of Range Cleared UPS Internal Configuration Failure UPS Internal Configuration Failure Cleared UPS Internal Failure UPS Internal Failure Cleared UPS Inverter Failure UPS Inverter Failure Cleared UPS Inverte...

Page 67: ...put Overload Level 1 UPS Output Overload Level 1 Cleared UPS Output Overload Level 2 UPS Output Overload Level 2 Cleared UPS Output Short Circuit UPS Output Short Circuit Cleared UPS Over Temperature UPS Over Temperature Cleared UPS Rectifier Failure UPS Rectifier Failure Cleared UPS Rectifier Overload UPS Rectifier Overload Cleared UPS Redundant Communication Lost UPS Redundant Communication Rest...

Page 68: ...Alert messages 68 UPS Site Wiring Fault UPS Site Wiring Fault Cleared ...

Page 69: ...UPS Load Segment 1 Is Off 8 UPS Load Segment 1 Is On 9 UPS Load Segment 2 Is Off 9 UPS Load Segment 2 Is On 10 UPS Load Segment 3 Is Off 10 UPS Load Segment 3 Is On 11 UPS On Boost Cleared 11 UPS On Boost 12 UPS On Buck Cleared 12 UPS On Buck 13 UPS Input Frequency Out Of Range Cleared 13 UPS Input Frequency Out Of Range 14 UPS AC Module Failure Cleared 14 UPS AC Module Failure 15 UPS Input AC Not...

Page 70: ...UPS Inverter Over Voltage 30 UPS Inverter Under Voltage Cleared 30 UPS Inverter Under Voltage 31 UPS Output Overload Level 1 Cleared 31 UPS Output Overload Level 1 32 UPS Output Overload Level 2 Cleared 32 UPS Output Overload Level 2 33 UPS Output Short Circuit Cleared 33 UPS Output Short Circuit 34 UPS Single Wave Load Fault Cleared 34 UPS Single Wave Load Fault 35 UPS DC Bus High Negative Voltag...

Page 71: ...nfiguration Failure Cleared 46 UPS Internal Configuration Failure 47 Emergency Power Off Cleared 47 Emergency Power Off 48 UPS Fan Failure Cleared 48 UPS Fan Failure 49 UPS Output Is Off 49 UPS Output Is On 50 UPS Internal Failure Cleared 50 UPS Internal Failure 51 UPS Battery Test Failure Cleared 51 UPS Battery Test Failure 52 UPS Output Overload Cleared 52 UPS Output Overload 53 UPS Over Tempera...

Page 72: ...r windows maximum HTTPS 3 browser windows maximum Languages English or Japanese Alarms Email SNMP trap web interface Log 400 measurements or events Server protection Up to 100 servers protected Network Fast ETHERNET 10 100 Mb s autonegotiation HTTP 1 1 SNMP V1 SNMP V3 NTP TFTP SMTP DHCP Identification User name and password Security SSL 3 0 TLS 1 0 Browsers Microsoft Internet Explorer 6 x or highe...

Page 73: ...ec Default Language English English Japanese Notified Application table empty NA Access control User name admin 10 characters maximum Password admin 10 characters maximum SNMP Community name read public 32 characters maximum Trap port 162 Not configurable SNMP Version V1 V3 Disabled V1 V3 V1 V3 Read Only User readuser 1 character minimum 32 characters maximum Read Only Security Level Authenticatio...

Page 74: ... 74 Parameter Default value Possible value Serial link Speed 9600 baud Not configurable Data bits 8 Not configurable Stop bits 1 Not configurable Parity without Not configurable Flow control without Not configurable ...

Page 75: ... ON server setup setting might be disabled Action In the server system BIOS change the setting for Automatic Power ON to Enabled Clients cannot communicate with UPS after swapping HP UPS Network Module with another UPS Possible Cause The HP UPS Network Module and Clients are configured with an old power source Action Reconfigure the HP UPS Network Module power source and then reconfigure the Clien...

Page 76: ...ers o Bits per second 9600 o Data bits 8 o Parity None o Stop bits 1 o Flow control None In the HyperTerminal window the UPS Network Module Bootloader prompts for a TFTP IP address 2 Setup a TFTP server 3 Copy the UPS Network Module firmware image file to the TFTP server default folder 4 Rename the UPS Network Module image file to image bin 5 Launch the TFTP 6 Enter the TFTP server IP address at t...

Page 77: ...rldwide in English webpage http welcome hp com country us en wwcontact html For HP technical support In the United States for contact options see the Contact HP United States webpage http welcome hp com country us en contact_us html To contact HP by phone o Call 1 800 HP INVENT 1 800 474 6836 This service is available 24 hours a day 7 days a week For continuous quality improvement calls may be rec...

Page 78: ...oth classes to bear a label indicating the interference potential of the device as well as additional operating instructions for the user FCC rating label The FCC rating label on the device shows the classification A or B of the equipment Class B devices have an FCC logo or ID on the label Class A devices do not have an FCC logo or ID on the label After you determine the class of the device refer ...

Page 79: ...2 this device must accept any interference received including interference that may cause undesired operation For questions regarding this product contact us by mail or telephone Hewlett Packard Company P O Box 692000 Mail Stop 530113 Houston Texas 77269 2000 1 800 HP INVENT 1 800 474 6836 For continuous quality improvement calls may be recorded or monitored For questions regarding this FCC declar...

Page 80: ... Norms that are listed in the EU Declaration of Conformity issued by HP for this product or product family and available in English only either within the product documentation or at the following HP website http www hp eu certificates type the product number in the search field The compliance is indicated by one of the following conformity markings placed on the product For non telecommunications...

Page 81: ...nd electronic equipment The separate collection and recycling of your waste equipment at the time of disposal will help to conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment For more information about where you can drop off your waste equipment for recycling please contact your local city office your household waste disposal service...

Page 82: ...Regulatory compliance notices 82 Class B equipment BSMI notice ...

Page 83: ...stem BOOTP Bootstrap Protocol DC domain controller DHCP Dynamic Host Configuration Protocol DNS domain name system HPPP HP Power Protector HTTP hypertext transfer protocol HTTPS hypertext transfer protocol secure sockets IP Internet Protocol IPv4 Internet Protocol version 4 IPv6 Internet Protocol version 6 ...

Page 84: ...t information base NTP network time protocol OS operating system SIM Systems Insight Manager SMS short message service SMTP Simple Mail Transfer Protocol SNMP Simple Network Management Protocol SSL Secure Sockets Layer TCP Transmission Control Protocol TFTP Trivial File Transfer Protocol UDP User Datagram Protocol ...

Page 85: ...Acronyms and abbreviations 85 UPS uninterruptible power system URL uniform resource locator USB universal serial bus ...

Page 86: ...t configuration 73 discovering the network module 49 DNS server 32 E Email Message Settings screen 44 Email Notification screen 42 email notifications setting up 42 European Union notice 80 Event Log screen 28 event log exporting 28 exporting a system log 29 exporting an event log 28 F factory default settings 73 factory defaults resetting 30 47 FCC rating label 78 features 6 11 Federal Communicat...

Page 87: ...uick setup overview 10 R redundant configuration 8 regulatory compliance identification numbers 78 regulatory compliance notices 78 80 required tools 12 requirements browser 9 resetting the system 30 47 restart settings 35 52 S Schedule Shutdown screen 26 screen resolution 9 secure sessions Firefox 18 secure sessions Google Chrome 19 secure sessions Internet Explorer 17 secure sessions Mozilla 18 ...

Page 88: ...ing the firmware 45 55 UPS alarms 65 UPS Alarms table 24 UPS Data Log screen 27 UPS Status table 23 UPS about 24 V views 19 W web interface requirements 9 web interface overview 16 web interface using and navigating 19 ...