Troubleshooting 76
•
Bits per second—9600
•
Data bits—8
•
Parity—None
•
Stop bits—1
•
Flow control—None
The default password to access the serial configuration menu is “admin”.
UPS Network Module fails to boot after upgrading the
firmware
Possible Cause:
The application might be corrupted due to an interruption while flashing the firmware.
Action:
1.
Using the supplied serial cable, connect to the UPS Network Module through a terminal emulation
program, such as HyperTerminal, with the following parameters:
o
Bits per second—9600
o
Data bits—8
o
Parity—None
o
Stop bits—1
o
Flow control—None
In the HyperTerminal window, the UPS Network Module Bootloader prompts for a TFTP IP address.
2.
Setup a TFTP server.
3.
Copy the UPS Network Module firmware image file to the TFTP server default folder.
4.
Rename the UPS Network Module image file to
image.bin
.
5.
Launch the TFTP.
6.
Enter the TFTP server IP address at the prompt on the terminal emulation program window.
7.
Press
Enter
.
UPS is not powered on after a scheduled shutdown
Possible cause:
The Restart time value might be configured as less than the Shutoff time value.
Action:
Configure the Restart time to a greater value than the Shutoff time value.