Systems Insight Manager integration 49
o
Event-based trap—A URL is included in each trap to link directly from HP SIM to the Overview screen
for the specific device for which the trap was sent.
Discovering the UPS Network Module
HP SIM automatically detects UPS Network Modules as part of the device discovery process. If detected, a
hyperlink is included on the HP SIM All Systems page for the UPS on which the UPS Network Module is
installed. The UPS Network Module should be installed and running before attempting discovery through HP
SIM.
If the defaults are not used, a new entry can be made to the additionalwsdisc.props file, located in the
CONFIG directory in the HP SIM install directory, to allow HP SIM to correctly discover and identify the UPS
Network Module. For more information on editing the additionalwsdisc.props file, see the
additionalwsdisc.txt file located in the same directory.
Example:
ADDITIONALWSDISC.PROPS file with UPS Network Module entry
# ----------------------------------------------------
# Additional Web Server Discovery Properties
#
# ----------------------------------------------------
# NOTE: See "additionalWsDisc_README.txt" for a description of entries in
# this file and how to add or remove additional web server ports used for
# discovery and identification.
# ----------------------------------------------------
#
# ----------------------------------------------------
# The following are actual web server ports enabled by default.
# To remove them from the discovery process, comment out the line with a '#'
# or remove it. You will need to restart the HP SIM service for
# the changes to take effect. In addition you will need to run the Device
# Identification task to find any new ports that were defined.
# ----------------------------------------------------
411=Director Agent, ,true,false, ,http
3201=Compaq TaskSmart, ,true,false, ,https
8008=Default Home Page, ,true,false, ,http
1311=Server Administrator, ,true,false, ,https
1234=HP UPS Network Module, ,true,false, ,https
The last entry allows HP SIM to detect a UPS Network Module running on port 1234 and using HTTPS
(Secure Socket Layer protocol).
HP SIM services must be restarted to apply the change.
Summary of Contents for UPS Network Module
Page 60: ...Firewall configuration 60 13 Click Change scope to add more security to the port exception ...
Page 63: ...Firewall configuration 63 ...
Page 68: ...Alert messages 68 UPS Site Wiring Fault UPS Site Wiring Fault Cleared ...
Page 82: ...Regulatory compliance notices 82 Class B equipment BSMI notice ...