Updating the firmware 55
Updating the firmware
Updating the firmware overview
Use the Firmware Upload screen (on page
45
) to update the UPS Network Module firmware.
During the boot process, if the UPS Network Module detects that the application is corrupted, you are
prompted to enter the TFTP server IP address. This process is only available when the application is
damaged.
To update the firmware image from the bootloader:
1.
Setup a TFTP server.
2.
Load the firmware image, and then rename the image to
image.bin
.
3.
Copy the
image.bin
file to the default directory.
4.
Be sure that you have connected the configuration cable ("
Connecting the configuration cable
" on
page
14
) to the UPS Network Module and the host computer.
5.
Launch a terminal emulation program, such as HyperTerminal ("
Launching a terminal emulation
program
" on page
14
). The following menu appears:
------------------------------------------------------------------------
-----
HP
NETWORK MANAGEMENT CARD
BOOTLOADER VERSION : 1.1
------------------------------------------------------------------------
-----
RAM autotest in progress.
RAM autotest SUCCESS.
Commercial reference : 66102
Kitting technical level : 12
Kitting revision : GD
Ethernet MAC Address : 00:20:85:FD:A1:9C
Serial number : BJ0L050LD
PHY autotest SUCCESS
The application in FLASH is corrupted !!!
Run the TFTP server to download the image.bin file
Set the TFTP server IP address :
6.
Enter the IP address of the TFTP server, and then press
Enter.
Summary of Contents for UPS Network Module
Page 60: ...Firewall configuration 60 13 Click Change scope to add more security to the port exception ...
Page 63: ...Firewall configuration 63 ...
Page 68: ...Alert messages 68 UPS Site Wiring Fault UPS Site Wiring Fault Cleared ...
Page 82: ...Regulatory compliance notices 82 Class B equipment BSMI notice ...