Configuration parameters 53
This following example describes the shutdown parameters for a UPS with two load segments, four
connected servers that have HPPP Clients installed on each server, and one UPS Network Module.
Item
Description
1
Utility failure
2
Utility restore
3
Utility
4
Client 1on load segment 1
5
Client 2 on load segment 1
6
UPS Network Module setting for load segment 1
7
Load segment 1
8
Client 3 on load segment 2
9
Client 4 on load segment 2
10
UPS Network Module setting for load segment 2
11
Load segment 2
12
UPS
On utility
On battery (SIA)
Operating system shutdown time (OST)
t1
Utility failure—UPS is on battery, and all servers are powered
as usual
t2
Shutdown process initiated—Shutdown scripts run,
applications close, and the operating system shuts down
t3
All servers are completely powered down. Load segments
power down, and then the UPS powers down.
t4
Utility restore
t5, t6, t7
The UPS, load segment 1, and load segment 2 are powered up