HP UPS Network Module web interface 25
Manual Control screen
Click
Manual Control
in the menu tree to display the Manual Control screen. This screen allows an
administrator to execute shutdown and restart sequences for the UPS and its controlled load segments. To
prevent data loss, configure the time required to shut down each registered server using the Shutdown
Parameters screen (on page
35
).
The status of each load segment is indicated by an icon. A green icon (
) indicates that the load segment
is on. A red icon (
) indicates that the load segment is off. A gray icon (
) indicates that the load
segment status is unknown.
IMPORTANT:
The UPS has priority over the controlled load segments. Shutting down the UPS
causes the load segments to shut down. Controlled load segments can only be restarted if the UPS
is on.
Only users with administrator privileges can save command parameters and execute commands. To
configure a command:
1.
Select the command you want to run in the Control pull-down menu. Configured commands will not
initiate until you click
Execute
.
o
Safe power down
—A shutdown sequence for the load segment is launched immediately.
Connected equipment powers off, and then the load segment powers off.
o
Safe power down & reboot
—A sequence containing a shutdown command followed by a restart
command for the load segment is launched immediately. Connected equipment powers off, and
then the load segment powers off. The load segment restarts when the Toggle Duration time is
reached.
o
Immediate On
—A restart sequence for the load segment is launched immediately. The load segment
powers on, and then connected equipment powers on.
o
Delayed, safe power down
—A shutdown sequence for the load segment is launched when the Off
Delay time is reached. Connected equipment powers off, and then the load segment powers off.
Summary of Contents for UPS Network Module
Page 60: ...Firewall configuration 60 13 Click Change scope to add more security to the port exception ...
Page 63: ...Firewall configuration 63 ...
Page 68: ...Alert messages 68 UPS Site Wiring Fault UPS Site Wiring Fault Cleared ...
Page 82: ...Regulatory compliance notices 82 Class B equipment BSMI notice ...