CAUTION:
When using a Compaq branded 7000 Series rack,
you must install the high airflow rack door insert [P/N 327281-B21 (42U)
or P/N 157847-B21 (22U)] to provide proper front-to-back airflow and
cooling.
CAUTION:
If a third-party rack is used, observe the following
additional requirements to ensure adequate airflow and to prevent
damage to the equipment:
•
Front and rear doors—If the 42U rack includes closing front and rear
doors, you must allow 5,350 sq cm (830 sq in) of holes evenly
distributed from top to bottom to permit adequate airflow (equivalent
to the required 64 percent open area for ventilation).
•
Side—The clearance between the installed rack component and the
side panels of the rack must be a minimum of 7 cm (2.75 in).
When vertical space in the rack is not filled by a server or rack component, the
gaps between the components cause changes in airflow through the rack and
across the servers. Cover all gaps with blanking panels to maintain proper
airflow.
CAUTION:
Always use blanking panels to fill empty vertical
spaces in the rack. This arrangement ensures proper airflow. Using a
rack without blanking panels results in improper cooling that can lead to
thermal damage.
Temperature requirements
To ensure continued safe and reliable equipment operation, install or position the
system in a well-ventilated, climate-controlled environment.
The maximum recommended ambient operating temperature (TMRA) for most
server products is 35°C (95°F). The temperature in the room where the rack is
located must not exceed 35°C (95°F).
CAUTION:
To reduce the risk of damage to the equipment
when installing third-party options:
Summary of Contents for ProLiant DL140
Page 5: ...Contents 5 Customer self repair 98 Acronyms and abbreviations 99 Index 105 ...
Page 6: ......
Page 16: ......
Page 20: ......
Page 31: ...Troubleshooting 31 1 ...
Page 33: ...Troubleshooting 33 2 ...
Page 37: ...Troubleshooting 37 4 ...
Page 39: ...Troubleshooting 39 5 ...
Page 90: ...90 HP ProLiant 100 Series Server User Guide Japanese notice BSMI notice ...
Page 94: ......
Page 104: ......