UDC 3300 Process Controller Product Manual
109
4.7 Output Algorithm Parameters Set Up Group
Introduction
This data deals with various output types in the controller, the Digital
Output Status, and the Current Duplex functionality.
Output algorithm
group prompts
Table 4-6 lists all the function prompts in the Output Algorithm Set Up
group and their definitions.
Table 4-6
Output Algorithm Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
OUT ALG
The OUTPUT ALGORITHM lets you select the type of
output you want. Not applicable with Control algorithm
prompt 3PSTEP.
Selections are hardware dependent. For example, if the
controller does not have a current output, then none of the
prompts for Output Algorithms that need a current output
will appear. Likewise, if the controller does not have a
relay output, then none of the prompts that need a relay
output will appear.
ATTENTION For all Duplex Output forms, PID heat
parameters apply for controller output greater than 50 %;
PID cool parameters apply for controller output less than
50 %.
TIME
TIME SIMPLEX—This output algorithm uses Digital
Output 1 for Time Proportional Control. The output is
updated per the Loop sampling rate selection. Time
Proportional Output has a resolution of 4.44 msec. Cycle
Time is adjustable from 1 to 120 seconds.
CURRNT
CURRENT SIMPLEX—Type of output using one 4 mA to
20 mA signal that can be fed into a positive or negative
grounded load of 0 to 1000 ohms. The signal can be
recalibrated for any desired range from 4 mA to 20 mA for
0 % to 100 % output.
POSITN
POSITION PROPORTIONAL SIMPLEX—Type of output
using two SPDT relays and a motor which has a 100 to
1000 ohms feedback slidewire.
Forces Input 2 to SLIDEW selection.
ATTENTION Position Proportional is not available on
two-loop or cascade controllers.
Other prompts affected: DEADBAND, IN2 TYPE
TIME D
TIME DUPLEX—This output algorithm uses Digital
Outputs 1 and 2 for Duplex Time Proportional Control. The
outputs are updated per the Loop sampling rate selection.
Time Proportional Output has a resolution of 4.44 msec.
Cycle Time is adjustable from 1 second to 120 seconds.
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......