UDC 3300 Process Controller Product Manual
231
7.6 Restoring Factory Calibration
How to restore it
The factory calibration constants for all the input actuation types that can
be used with the controller are stored in its nonvolatile memory. Thus,
you can quickly restore the “Factory Calibration” for a given input
actuation type by simply changing the actuation type to another type and
then changing it back to the original type. See Table 7-6 for the procedure.
Procedure
Table 7-6 lists the procedure for restoring factory calibration.
Table 7-6
Restoring Factory Calibration
Step
Operation
Press
Action/Result
1
Set LOCKOUT
to CALIB or
NONE
SET
UP
until you see:
Upper Display
Lower Display
SET UP
TUNING
FUNCTION
LOOP 1/2
until you see:
Upper Display
Lower Display
LOCKOUT
One of the following
NONE
CALIB
+CONF
+VIEW
MAX
or
Until CALIB or NONE is in the upper display.
2
Enter
INPUT 1 or 2
Setup Group
SET
UP
until you see:
Upper Display
Lower Display
SET UP
INPUTn
n = 1, 2, or 3
FUNCTION
LOOP 1/2
until you see:
Upper Display
Lower Display
IN nTYPE
Current Selection
n = 1, 2, or 3
or
to change the current selection to another
selection.
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......