Output Algorithm Parameters Set Up Group
Introduction
This data deals with various Output types that are available for use in the
controller. It also lists the Digital Output Status, the Current Duplex
functionality, and Relay Time Cycle increments.
Function prompts
Table 3-8 lists all the function prompts in the Output Algorithm Set Up
group.
Table 3-8
Output Algorithm Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
OUT ALG
Loop 1 Output Algorithm
TIME
Time Simplex
CURRNT Current Simplex
POSITN
Position Proportional
TIME D
Time Duplex
CUR D
Current Duplex
CUR TI
Current/Time Duplex
TI CUR
Time/Current Duplex
CURRNT
Section
4.7
4–20 RNG
Current Duplex Range
100PCT
50 PCT
100PCT
OUT2 ALG*
Loop 2 Output Algorithm
NONE
TIME
CURRNT
CUR D
CUR TI
TI CUR
CURRNT
RLYSTATE
Digital Output State at 0 %
Output
1OF2OF
(Output relays 1 and 2 are
both de-energized)
1ON2OF
(Output relay 1 is
energized, output relay 2
is de-energized)
1OF2ON
(Output relay 1 is de-
energized, output relay 2
is energized)
1ON2ON
(Output relays 1 and 2 are
both energized)
1OF2ON
RLY TYPE
Relay Cycle Time Increments
MECHAN
(Cycle time in one second
increments)
SOL ST
(Cycle time in 1/3 second
increments: 1 = .33
seconds, 120 = 40
seconds)
MECHAN
*Not available on DC330B
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......