5.19 Auto/Manual Station
Introduction
When you select “AM STA” (auto manual station) under the Option Set
Up group function prompt “DIG IN1” or “DIG IN2” (digital input option),
contact closure on the selected digital input causes the controller to switch
to Auto/Manual Station mode.
Function
As shown in Figure 5-5, State 2 is the “A/M Station mode” where the
programmable logic controller (PLC) output is sent through the
Auto/Manual Station. You can switch to manual and change the output at
the controller. (It uses PID set 2.)
State 1 is the “Backup PID mode” which is triggered by opening the
digital input. (It uses PID set 1.)
Figure 5-5
Auto/Manual Station and Backup Control Feature
T/C
T/C
PLC
PV
SP
IN1
IN2
PID A
OUT1
OUT1
Output 1
4-20 mA
To valve
Aux
Output
SP1 =
new
selection
DI #1 = "AM STA"
(new
selection)
State 1:
DI #1: Open
BACKUP
PID
CONTROL
State 2:
DI #1: Closed
A/M STATION
LSP = SP1
LSP = 2SP
– Direct action
– PD+MR
– SP = 2SP
– PV = IN2
– PIDSET2
PIDSET1
P =
I =
D =
same
as
PLC
Configure
State 2 per
next page.
Control output
4-20 mA
PV
PV
Alarm
Output on
Manual
Mode
(new
selection)
PD+MR
}
24184
OPEN
CLOSED
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......