4/00
UDC 3300 Controller Product Manual
157
What happens when
you change modes
Table 5-8 explains what happens to the controller when you switch from
one mode to another.
Table 5-8
Changing Operating Modes
Mode Change
Description
Manual to Automatic
Local Setpoint
The Local Setpoint is usually the value previously stored as
the Local Setpoint.
PV tracking is a configurable feature which modifies this.
For this configuration, when a loop is in manual mode, the
local setpoint value tracks the process variable value
continuously.
Manual or Auto Local to
Automatic Remote SP
The Remote Setpoint uses the stored ratio and bias to
calculate the control setpoint.
Auto bias is a configurable feature which modifies this.
When it is selected the transfer from automatic local to
automatic remote or from manual remote to automatic
remote adjusts the bias based on the local setpoint such
that Bias = LSP – (RSP Input x R).
Automatic Remote
Setpoint to Manual or
Auto Local Setpoint
If configured for Local Setpoint Tracking, when the
controller transfers out of remote setpoint the last value of
the control setpoint is inserted into the local setpoint.
If LSP tracking is not configured, the local setpoint will not
be altered when the transfer is made.
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......