4/00
UDC 3300 Process Controller Product Manual
43
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
RUN HOLD**
Run/Hold Key Lockout
DISABL
ENABLE
ENABLE
Section
4.2
PVEUVAL1
PVEUVAL2
PVEUVAL3
PVEUVAL4
PVEUVAL5
PVEUVAL6
PVEUVAL7
PVEUVAL8
PV1 (through PV8) Value for
Gain Scheduling
PV value within the PV limits.
In engineering units
0
GAINVAL1*
GAINVAL2*
GAINVAL3*
GAINVAL4*
GAINVAL5*
GAINVAL6*
GAINVAL7*
GAINVAL8*
Gain 1 (through Gain 8)
Value for Gain Scheduling
0.001 to 1000 floating
Gain or Proportional Band
1.000
* ATTENTION If units of percent proportional band (PB) are selected under the Control Set Up prompt, function
prompt PBorGAIN, then the displayed values are in %PB, but the lower display will still show Gain.
**Only appears if LOCKOUT = NONE.
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......