Refer to the Modbus Master Installation Instructions that are on the CD to help set up
other modbus devices to talk to the recorder. (43-TV-33-89 - 43-TV-33-102).
Master
•
Enabled
- Toggle On to make this recorder a Master device
•
Poll Rate
- Enter a time period in seconds of how often there is a request for data
•
Legacy Ethernet
- Tick this to connect to
Honeywell V5
recorders.
•
Slave 1 ..32
- Up to 32 slaves can be setup per master device. Setup each Slave in turn
starting with number 1.
• • Enabled - Toggle On to enable Slave #
• • Friendly name - Enter a name to easily identify this slave device
• • ID - This is to connect to slave ID
• • Port - Select this for a list of available ports, either Ethernet or RS485. For port
configuration see
• • Network Name - (Ethernet only). Enter the recorders IP address or the Network
name, eg. xs-nnnnnn, where nnnnnn is the recorder’s 6-digit Serial number.
for the recorder’s IP address and serial number.
• • Protocol - Select this for a list of available protocols. Modbus or Modbus X*.
Modbus and Modbus X can both use Ethernet or RS485 Ports. Protocols define
the format in which the data is transferred from the recorder to a PC or transfer
between other devices and peripherals. FPLB – Floating Point Little Endian
Byte Swapped Format & FP B - Floating Point Big Endian Format are standard
notations
.
• • Transaction 1 ..8 - A request for a register or set of contiguous registers
Enabled
- Toggle On to enable the first transaction request
Direction
- Direction for the data to flow; In to or Out from the recorder
Command
- This is the type of Registers used by the slave device. Refer to the
individual memory map for the register type used for each type of device.
Data Type
- Refer to individual memory maps for each type of device to deter-
mine the type of data. Eg.
signed 16-bit int, unsigned 16-bit int
or IEEE
float.
X Series
devices use IEEE float.
Start Addr
. - This is the register address number to start the transaction from
No. Of Items
- Enter the number of items from the start address that are
included in the transaction. For example displayed here will be
10 SCV[1,1,1] - [1,1,10].
This means the transaction will take 10 items from the start address with a
Serial Comms variable of Slave [1], Transaction [1], Register [1] - to Slave [1],
Transaction [1], Register [10]
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......