43-TV-25-30 Iss.6 GLO Aug 07 UK
61
•
Update Rate
- Fixed at 1Hz
•
Label -
Select and enter an identification label for the pulse input. Select and enter a
label. Up to 16 characters.
When the configuration is complete select the Finish button to Commit, Discard or Commit
Later. Select the Back button to return to the previous menu.
Linearisation Tables
(Main Menu > Configure > Setup > Edit Setup> Field I/O > Linearisation)
Linearisation Tables
- To be used with Analogue Input type Volts, Amps or Ohms.
These are user defined tables that can be set up to allow a non-linear input signal to be dis-
played on the recorder. By entering a set of non-linear signal input values (X) into the line-
arisation table, the recorder will use the table to generate linear output (Y) in engineering
units, to be displayed and/or log on the recorder.
• Select the next available table and rename it for ease of identification by selecting the
name button.
• Select the Values button to take you to the start of a new table. Press the Add button to
produce the first line. More than one set of points are required to do the conversion.
• Click into the text entry boxes under the X and Y boxes and enter the required values
(or leave it if your table starts at 0). The Signal Input (X) goes in the first column and the
Engineering units (Y) in the second column.
• To add a line at the bottom, click on Add. To ad a line above or below, click on a line and
use the Insert Above and Insert Below buttons. To delete a line, click in the line and
select Delete.
• When you have finished your table select the tick box, this will also verify the table and
produce a Data Error box if there are any problems.
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......