300
43-TV-25-30 Iss.6 GLO Aug 07 UK
•
Low Eng
- (only available when Dual point is selected). Set the Low limit for the Engineer-
ing units.
•
Low Offset
- enter an offset value that is offset against the Low Eng value.
•
High Eng
- (only available when Dual point is selected). Set the High limit for the Engineer-
ing units.
•
High Offset
- enter an offset value that is offset against the High Eng value.
-10V
+10V
-10V
+10V
Single Point Sensor Compensation is
used to offset the signal input by a user
specified amount over the full range.
Dual Point Sensor Compensation is used to
offset the signal input by a user specified
amount against the Low and High Eng val-
ues. The offset amount can vary throughout
the signal input range.
Solid line shows without compensation
and dotted line shows with compensation
Low Offset of 5
High Offset of -5
Figure App H.21 Sensor Compensation
100 High Eng
0 Low Eng
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......