43-TV-25-30 Iss.6 GLO Aug 07 UK
257
Latched or Single Pulse
The relay outputs can be set by the user to be either Latched or Single Pulse.
Latched
A latched relay will maintain in its active state until the trigger source has returned to a non
alarmed state, or a second Event has been activated to disable the relay.
Single Pulse
The relay will go active for a period of time, specified by the user, then return to a non active
state. The time out period remains independent of the length of time the active state re-
mains.
Single Pulse Relay Settings
User can specify Pulse length in seconds from 0.1 (100ms) to 6480 (108 minutes) in 0.1 sec-
ond increments.
Fail Safe
Each relay channel can be independently selected with the fail safe option. This will invert
the state of the relay output. With Failsafe Off normally open (NO) relays have open contacts
when the power is off, and open contacts when there is no active alarm. The contacts will
close when an associated alarm goes active. With Failsafe On, normally open relays have
closed contacts when the recorder is powered on and there are no open active alarms, and
the contacts open with an alarm active or when the power is removed.
Relay Output Specification
The
Minitrend QX
recorder will provide the ability to have at least 1 relay output for each
analogue input (i.e. 16).
Multitrend SX
recorder will also provide at least one relay output
for each analogue input (i.e. 48), there are three available slots for Digital inputs/ Relay Out-
puts. Up to 8 relay outputs are available for the
eZtrend QXe
recorder.
Common Alarm Output
(Not available for the
eZtrend QXe
recorder)
The common alarm output include a single alarm relay. This relay is the same rating as
those on the 8 & 16 Digital I/O cards. This relay is NC (normally closed) and can be activated
by any alarm. This relay will close when power is removed. This relay is identified as “Fixed”
in the relay output pick lists.
• Rating - 24Vdc 1A Resistive Load
Digital Input Cards
Three options for digital inputs are available
8 Digital Inputs
8 Digital I/O card, this 8-channel card allows the user to configure each channel to be either
relay output or digital input. Relay output rated at 24V DC 1 Amp rated (resistive load).
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......