3 Default Configuration
NOTE:
Oxygen levels are 20.9% v/v in a normal atmosphere, equivalent to 17.3 mA. Use caution when
integrating an oxygen Midas unit using the 4-20 mA output since fault, inhibit, and no power conditions
are below 4 mA and, by default, an oxygen depletion alarm is triggered on a falling alarm (default 19.5%
v/v). In that case, Honeywell Analytics recommends one of the following:
• Use Modbus TCP digital communications
• Use discrete relay inputs instead of a 4-20 mA signal to trigger gas alarms
• Program the control system of the 4-20 mA input with logic and a delay (e.g., 1 second) before
triggering an alarm to determine if the 4-20 mA output is at one of the 0-4 mA conditions described
above.
Contact Honeywell Analytics for further information.
The Midas
®
gas detector is factory-configured as described in Table 3-1 on the following page.
Summary of Contents for Midas
Page 7: ...Midas Gas Detector 1 1 1 Description ...
Page 9: ...Midas Gas Detector 2 1 2 Overview ...
Page 14: ...Midas Gas Detector 3 1 3 Default Configuration ...
Page 17: ...Midas Gas Detector 4 1 4 Installation ...
Page 41: ...Midas Gas Detector 5 1 5 Startup ...
Page 43: ...Midas Gas Detector 6 1 6 Operation ...
Page 53: ...Midas Gas Detector 7 1 7 Navigating Modes and Submenus ...
Page 74: ...Midas Gas Detector 8 1 8 Maintenance ...
Page 82: ...Midas Gas Detector 9 1 9 Pyrolyzer Module Options ...
Page 89: ...Midas Gas Detector 10 1 10 Optional LonWorks Interface Installation ...
Page 99: ...Midas Gas Detector 11 1 11 Troubleshooting and Fault Diagnosis ...
Page 102: ...Midas Gas Detector 12 1 12 REFLEX ...
Page 104: ...Midas Gas Detector 13 1 13 Internal Web Server ...
Page 106: ...Midas Gas Detector 13 3 Diagram 13 1 IPAddress setting in Windows XP ...
Page 129: ...Midas Gas Detector 14 1 14 Typical Installation Topologies ...
Page 132: ...Midas Gas Detector 15 1 15 Ordering Information ...
Page 136: ...Midas Gas Detector 16 1 16 Specifications ...
Page 139: ...Midas Gas Detector 17 1 17 Calibration and Bump Testing ...
Page 143: ...Midas Gas Detector A 1 A Modbus TCP Interface ...
Page 150: ...Midas Gas Detector B 1 B Gas Tables ...
Page 158: ...Midas Gas Detector C 1 C Warranty ...