Midas
®
Gas Detector
10-3
Diagram 10-2. LonWorks Cable Gland.
10.1.2 Wiring the Midas
®
for LonWorks
®
Wiring Diagram
Plug 2
Plug 1
Pwr +24 VDC
Lon A
Lon B
Pwr Common
Pwr +24 VDC
Lon A
Lon B
Pwr Common
Wiring Notes:
1. Maximum wire size is 16 AWG.
2. Input voltage range is 20.4 to 26.4 VDC. Midas
pyrolyzers and transmitters with LonWorks
modules have a restricted minimum voltage
requirement of 21.6 VDC.
3. It is mechanically possible to misalign Plug1
and Plug2. Care must be taken when inserting
plug to assure correct alignment.
4. Plug1 and Plug2 are internally connected in
parallel to facilitate wiring in bus topology.
5. LonWorks
®
FT-10 wiring is polarity sensitive.
Lon A and Lon B may be swapped.
10.1.3 Configuring the Midas
®
for LonWorks
®
1. Turn on 24 VDC power.
2. Confirm that the Midas
®
initiates the power up
sequence.
3. Reset Fault F49 if present.
4. Set alarm levels and other parameters as
desired.
5. Confirm that the Midas
®
IP parameters are at
default values. If changed, the DHCP client
must be set to ‘n’. The IP address must be
restored to 169.254.60.47 and the subnet
mask must be restored to 255.255.255.0
Summary of Contents for Midas
Page 7: ...Midas Gas Detector 1 1 1 Description ...
Page 9: ...Midas Gas Detector 2 1 2 Overview ...
Page 14: ...Midas Gas Detector 3 1 3 Default Configuration ...
Page 17: ...Midas Gas Detector 4 1 4 Installation ...
Page 41: ...Midas Gas Detector 5 1 5 Startup ...
Page 43: ...Midas Gas Detector 6 1 6 Operation ...
Page 53: ...Midas Gas Detector 7 1 7 Navigating Modes and Submenus ...
Page 74: ...Midas Gas Detector 8 1 8 Maintenance ...
Page 82: ...Midas Gas Detector 9 1 9 Pyrolyzer Module Options ...
Page 89: ...Midas Gas Detector 10 1 10 Optional LonWorks Interface Installation ...
Page 99: ...Midas Gas Detector 11 1 11 Troubleshooting and Fault Diagnosis ...
Page 102: ...Midas Gas Detector 12 1 12 REFLEX ...
Page 104: ...Midas Gas Detector 13 1 13 Internal Web Server ...
Page 106: ...Midas Gas Detector 13 3 Diagram 13 1 IPAddress setting in Windows XP ...
Page 129: ...Midas Gas Detector 14 1 14 Typical Installation Topologies ...
Page 132: ...Midas Gas Detector 15 1 15 Ordering Information ...
Page 136: ...Midas Gas Detector 16 1 16 Specifications ...
Page 139: ...Midas Gas Detector 17 1 17 Calibration and Bump Testing ...
Page 143: ...Midas Gas Detector A 1 A Modbus TCP Interface ...
Page 150: ...Midas Gas Detector B 1 B Gas Tables ...
Page 158: ...Midas Gas Detector C 1 C Warranty ...