Midas
®
Gas Detector
3-3
Table 3-1. Midas
®
default configuration
Current source with:
1.0 mA Fault
2.0 mA Inhibit
3.0 mA Maintenance Fault
4.0 to 20.0 mA Gas reading (normal operation)
21.0 mA Over range
Toxic Gas
Flammable Gas
Oxygen
Full Scale (FS)
Typically 4 x Threshold Limit
Value (TLV)
100% Lower Explosive Limit
(LEL)
1
25% Volume (v/v)
Lowest Alarm Level (LAL)
Typically 1/2 TLV
10% LEL
5% v/v
Alarm 1
(Relay 1)
1/2 TLV
10% LEL
23.5% v/v (Rising)
Normally de-energized, energizes on alarm.
Contact Normally Open (NO), closes on alarm.
Alarm 2
(Relay 2)
TLV
20% LEL
19.5% v/v (Falling)
Normally de-energized, energizes on alarm.
Contact Normally Open (NO), closes on alarm.
Fault
(Relay 3)
Normally energized, de-energizes on fault.
Contact Normally Open (NO). Instrument Fault Only
Latching
Latching. Alarm and fault relays DO NOT automatically reset when reading falls below alarm
thresholds. Relays MUST be manually reset.
Pass code
No pass code set.
IP Address
169.254.60.47 subnet mask 255.255.255.0
1
Midas
®
detectors are not ETL approved for monitoring in or sampling from classified areas above 25% LEL
See
Table 7-3
for more information on Relay Configuration
Summary of Contents for Midas
Page 7: ...Midas Gas Detector 1 1 1 Description ...
Page 9: ...Midas Gas Detector 2 1 2 Overview ...
Page 14: ...Midas Gas Detector 3 1 3 Default Configuration ...
Page 17: ...Midas Gas Detector 4 1 4 Installation ...
Page 41: ...Midas Gas Detector 5 1 5 Startup ...
Page 43: ...Midas Gas Detector 6 1 6 Operation ...
Page 53: ...Midas Gas Detector 7 1 7 Navigating Modes and Submenus ...
Page 74: ...Midas Gas Detector 8 1 8 Maintenance ...
Page 82: ...Midas Gas Detector 9 1 9 Pyrolyzer Module Options ...
Page 89: ...Midas Gas Detector 10 1 10 Optional LonWorks Interface Installation ...
Page 99: ...Midas Gas Detector 11 1 11 Troubleshooting and Fault Diagnosis ...
Page 102: ...Midas Gas Detector 12 1 12 REFLEX ...
Page 104: ...Midas Gas Detector 13 1 13 Internal Web Server ...
Page 106: ...Midas Gas Detector 13 3 Diagram 13 1 IPAddress setting in Windows XP ...
Page 129: ...Midas Gas Detector 14 1 14 Typical Installation Topologies ...
Page 132: ...Midas Gas Detector 15 1 15 Ordering Information ...
Page 136: ...Midas Gas Detector 16 1 16 Specifications ...
Page 139: ...Midas Gas Detector 17 1 17 Calibration and Bump Testing ...
Page 143: ...Midas Gas Detector A 1 A Modbus TCP Interface ...
Page 150: ...Midas Gas Detector B 1 B Gas Tables ...
Page 158: ...Midas Gas Detector C 1 C Warranty ...