Rev. B
7-24
HMXMC001013
31-Mar-06
7.7
EXTERNAL ALARM INPUTS, CONTINUED
7.7.8
Disable PTZ Tamper
Often the PTZ site tamper alarm input is not used. As the tamper input is a normally-
closed input, sometimes PTZ sites are installed in the field with this tamper input open-
circuit. When the video system is turned-on the PTZ site generates an immediate site
tamper alarm. As the tamper input is actually a remote alarm input (number 8), it can be
defined into the alarm table as a general remote alarm input. The video system will then
ignore it as a default tamper alarm, as it is now being used for another purpose.
By making the definition a non-display type, the default tamper alarm can be essentially
disabled.
7.7.9 VideoBlox
Configuration
Video blox Alarm Module (
I
2
C16
) is connected to Port 5 of MAXPRO-Net Server. When
the alarm is generated, the macro at line number 100 will be executed. When the alarm
is cleared, the macro at line number 201 will be executed.