Malfunctions
HON 512 with HON 650 pilot user manual
64
Malfunction
Possible causes
Correction
Pilot: The diaphragm is defective
Perform maintenance on the pilot
as specified in
Maintaining the pilot
(see page 102)
Filter: The filter is dirty
Perform maintenance on the filter
as specified in the “Maintaining the
filter” section in
Maintaining the
pilot
(see page 102)
Actuator assembly: The diaphragm
is defective
Perform maintenance on the
actuator assembly as specified in
the
Maintenance
(see page 65)
section
Unstable outlet pressure
behavior (oscillations)
Pilot: Excessive amplification
Adjust the amplifying valve as
specified in
Adjusting the amplify-
ing valve
(see page 59)
The actuator assembly is operating
in the reseating pressure range
Check the design specifications;
contact the manufacturer if neces-
sary
The visual position indica-
tor is not working
Position indicator: The magnetic
ring is jammed
Perform maintenance on the
position indicator as specified in the
Maintenance
(see page 65) section
Position indicator: The spring is
damaged or not in place
Perform maintenance on the
position indicator as specified in the
Maintenance
(see page 65) section