Maintenance
HON 512 with HON 650 pilot user manual
137
8.4.6
Maintaining the fine mesh filter
Observe the following cleaning instructions:
▪
Before assembly, all parts must be cleaned in order to remove any foreign particles
(swarf) and soiling.
▪
If fasteners (screws, washers, etc.) are replaced with identical new parts, any oil on
these new parts must first be removed.
Observe the tightening torques below when following the instructions in this section:
Part
Tightening torque
Step
Base plate hex nut
10 Nm (8 ft lbs)
7
Fitting
40 Nm (30 ft lbs)
9
Proceed as follows:
Figure
Step
Description
1
Unscrew the nuts (1) and washers (2).
Remove the base plate (3) from the body.
2
Remove the filter insert (1) and clean it.
3
Check the filter cartridge for damage and
replace it with a new one if necessary.
4
Replace the O-ring (1) in the body with a
new, greased O-ring.
Cleaning
Tightening torques
Maintaining the filter