Maintenance
HON 512 with HON 650 pilot user manual
126
Figure
Step
Description
3
Unscrew the fitting (1) on the upper cover.
Replace the sealing ring (2) with a new,
greased sealing ring.
Lubricate the thread surfaces.
Screw the fitting (1) back in.
4
Remove the spring from the cap.
5
Loosen the screws and slowly and carefully
remove the lower cover.
Important!
While
removing the cover, parts on the inside
may fall out from the spring housing by
accident!
6
Remove the lower spring plate (1), the
axial washers (2), and the axial needle
roller bearing (3) from the spring housing.
7
Remove the compression spring (1) and
the upper spring plate (2) from the spring
housing.