![Honeywell Elster EK280 Applications Manual Download Page 52](http://html.mh-extra.com/html/honeywell/elster-ek280/elster-ek280_applications-manual_151826052.webp)
EK280
Application Manual
50
6.5.1 Parameterizing by keyboard
i
The use of enSuite parameterizing software is strongly recommended for parameterizing a
status output (see below).
Parameterization with the keyboard on the EK280 is described below.
a) Setting up the output mode:
−
Move the cursor to the tab "
Serv.
" and subsequently via the following path to the mode for the
corresponding output
"
Md.O1
"
to
"
Md.O4
"
:
Serv.
Outputs
Output 1
Md.O1
Serv.
Outputs
Output 2
Md.O2
Serv.
Outputs
Output 3
Md.O3
Serv.
Outputs
Output 4
Md.O4
i
The low-frequency event outputs of the EK280 can be operated with active or inactive
logic.(as a make contact or break contact). The output mode must be programmed accordingly
for this purpose (
below).
−
Press the ENTER key.
⇒
The set value flashes.
−
Press down one of the arrow keys
and/or
press repeatedly until the text
„
Event(C)
“
or
„
Event(O)
“
flashes.
Whereby:
"(C)" = closer: When the message is activated, the output is switched on (closed).
"(O)" = opener: When the message is activated, the output is switched off (opened).
−
Press the ENTER key to confirm the set value. It is possible to abort the entry by pressing the ESC
key.
b) Setting the status display for the output:
−
In the corresponding output menu press the
key repeatedly until
"
SpO1
",
"
SpO2
",
"
SpO3
", or
"
SpO4
" is displayed.
−
Press the ENTER key.
⇒
The set value flashes.
−
Move the cursor with the arrow keys
or
to the digits and change these with the arrow keys
or
to a value that is specified in the table.
2
For software versions prior to V2.50,
"Event+"
(event +) is displayed.
3
For software versions prior to V2.50,
"Event-”
(event -) is displayed.