EK280
Application Manual
171
Register
Address
Short
Desc.
Designation / value
Format
Unit
LIS200
Address
817
SNo
Device number (serial number)
16
1:180
820
DayB
Daily limit
12
2:141_1
Table 1: Standard Modbus table
(the register number is based on the physical address form)
The Modbus register assignment can be updated using the enSuite parameter software i.e. via the optical
interface.
8.1.2 Formats
Meanings of formats used:
Format Description
Format Description
3
Ushort, 16 Bit
16
Array6, BCD, 12 Bit
4
Ulong, 32 Bit
17
Array8, BCD, 16 Bit
9
Counter6
32
IEEEfloat, 32 Bit
12
Array2, BCD, 4 Bit
Code
Format
Number of registers
a) binary formats:
3
Number
1
Value
4
Number
2
MS Word
LS Word
upper part
lower part
32 Exponential
2
MS Word
LS Word
Bit 31
Bit 30…23
Bit 22…16
Bit 15...0
Sign
Exponent
Mantissa
upper part
Mantissa
lower part
9
Counter
3
MS Word
...
LS Word
Pre-decimal
position upper
part
Pre-decimal
position lower
part
Fractional digits
b) decimal formats:
17
BCD
numerator *
4
MS Word
...
...
LS Word
Pre-decimal position
Fractional digits
BCD time
stamp *
4
MS Word
...
...
LS Word
CCYY **
MMDD **
hhmm **
ss00 **
16 BCD number
3
MS Word
...
LS Word
12 digits
12 BCD time
1
hhmm **
*
Counter or time stamp, depending on assigned LIS
-
200 Address (
below)
**
CC = century, YY = year, MM = month, DD = day, hh = hour, mm = minute, ss = second