Message Status Name
Description, Procedure
6
St.7
p Warn Lim..
The measured gas pressure is outside the set warning limit values.
The warning limits can be adjusted using the parameterization
program enSuite.
6
St.9
z Warning
The sum of the gas analysis values for AGA-8 DC92 is more or
less than 100%. An accurate calculation of the real gas factor and
the compressibility ratio factor can therefore not be carried out.
7
StSy
Softw. error
This message is used for factory diagnosis.
Please contact Honeywell Technical Assistance Center.
7
StSy 2
Update error
Before the software update, an error was detected in the cached
software image.
8
StSy
Sett. error
The programing of the device has generated an unusable
combination of settings.
Contact the Honeywell Technical Assistance Center.
8
St.1
I1 Warn.sig.
When an input is configured as a warning input, if an active signal
is present on the relevant terminal (i.e., terminal DE2) this
message is displayed.
The input configuration can be adjusted using the
parameterization program enSuite.
8
St.2
I2 Warn.sig.
8
St.3
I3 Warn.sig.
8
St.4
I4 Warn.sig.
8
St.9
I5 Warn.sig.
8
St.10
I6 Warn.sig.
8
St.6
T2 Warn Lim.
The measured gas temperature of the second sensor is outside
the set warning limit values.
The warning limits can be adjusted using the parameterization
program enSuite.
8
St.7
p2 Warn Lim.
The measured gas pressure of the second sensor is outside the
set warning limit values.
The warning limits can be adjusted using the parameterization
program enSuite.
9
StSy
Batt. low
The remaining battery power is less than six months.
The batteries need to be changed soon.
9
St.3
TA Warn Lim.
The measured ambient temperature is outside the set warning limit
values.
The warning limits can be adjusted using the parameterization
program enSuite.
c) Remarks
10
StSy
Repair mode
The device is in revision mode.
11
StSy
Clock n. set
The internal clock of the volume corrector has not been adjusted
at the factory.
11
StSy 2
U.Logb. full
The software update log is full. An update is only possible if the
content of the software update log has been deleted.