EK280
Application Manual
46
Key for the status pointer SpO:
a.mm_0s:b.c
c = 0: Message comes, c = 1: Message comes or goes
b = 1: Instance status, b = 2: System or overall status
s = status number (1...9 for St.1 ... St.9
* mm = message number (1...16),
a = 0: a message mm, a = 1: Message group from message 1 to mm
Examples
Sc.O…
Description
0.mm_0s:1.1 *
A report in a Status
St.1
to
St.9
0.mm_02:2.1 *
A report in system status
StSy
0.mm_01:2.1 *
A report in overall status
Stat
1.mm_0s:1.1 *
Message group in system status
StSy
1.mm_02:2.1 *
VmD:
Actual volume disturbance quantity
1.mm_01:2.1 *
Message group in overall status
Stat
−
* mm = report-number (1...16), s = status number (1...9 for St.1 ... St.9)
6.3.2 Parameterizing with enSuite
The setting of the required report (or range) in particular can be conveniently set with enSuite.
−
The paths which are described below can be found in
enSuite
under:
"
Parameterize online
" > "
Parameters
" > "
Outputs
"
−
Setting up the output mode:
−
First of all, the mode must be set to the required value:
""
(Logic active: message is active, when the output is switched on.) or
−
"status-"
(Logic inactive: Report is active, when the output is switched off.)
a) Setting up the status pointer
for the output:
−
Under the menu heading "Status pointer for output x" operate the button with the 3 dots
:
−
If a specific single report is to be used as the reason for switching the output, make sure that the
marking "
Message range
" (see below) in enSuite is switched off.
−
Now the desired report can be clicked directly. The input is confirmed with "OK": in the example the
input 4 is used as incoming report, and this is then to be passed on via output 4 (for easier
understanding, the non-relevant reports have been masked):