![Honeywell Elster EK280 Applications Manual Download Page 197](http://html.mh-extra.com/html/honeywell/elster-ek280/elster-ek280_applications-manual_151826197.webp)
EK280
Application Manual
195
−
Move the cursor to
"Serv."
>
"Archives" > "FrMP".
−
Press the ENTER key.
⇒
"0"
flashes.
−
Change the value using the arrow keys
or
to
"1"
.
−
Press the ENTER key to confirm the set value. It is possible to abort the entry by pressing the ESC
key.
On the basis of the event "Ev" stored as a triggering event the data row indicates whether it was stored
automatically due to the elapsed measurement period or by triggering the
"FrMP"
.
9.1.7 Delete measurement period archive
2.4.2 Clear volumes and archives ("Clr.V")
2.4.3 Clear archives ("Clr.A")
9.2 Daily archive
In the daily archive meter readings and measured values are archived in regular daily period
"DayB"
.
The content of the daily archive can be shown on the display of the device via the path
"Serv." > "Archives" >
"Daily Archive"
.
i
The daily archive period archive is a flexible archive.
Archive contents and the memory capacity can be adapted with corresponding settings via
parameterization software enSuite when the administrator lock is open.
Our applications team is available if you require further information.