EK280
Application Manual
106
The Ethernet adapter in EM260 is basically parameterized at the Honeywell factory, so that at the time of
commissioning on site only the following, application-specific parameters need to be set.
−
IP address
−
Gateway address
−
Subnet mask
−
TCP-Port
These parameters may be set as follows in the Ethernet adapter:
−
Make sure that the EM260 is switched off.
−
Connect a PC with enSuite installed to the EK280 optical interface using the connection cable.
−
Start enSuite and establish the communication link to theEK280 via the optical interface.
(
3.1 Setting up the communication link to the EK280 via optical interface
−
Select "
Navigation
" on the left-hand side of the enSuite window and then "
Parameterize online
" at
the bottom of the navigation window.
−
In the top of the device window open the path "
Parameters
" > "
Interfaces
" by clicking on the relevant
plus signs, and then select "
Call time windows
”
−
Make sure that time windows 5 and 6 are closed.
−
In the path "
Parameters
" > "
Interfaces
" choose the option "
Terminal interface.
” select the
"Ethernet"
menu
.
Now enter your individual address parameters (IP, subnet mask, gateway, port) in the corresponding
parameter fields. Where necessary, you may require permission from your network administrator at
this time
Example parameters
−
Press the button
"
Transfer values to device
", so that the modified values are transferred into the
EK280.
−
Make sure that the EM260 is connected to the EK280 in accordance with
−
Make sure that in the EM260 the Jumpers J1, J2 and J3 are each in the uppermost position
(
picture).