Honeywell
CD3200 up to110A
User’s Manual ver. 2.0
www.honeywell.com/imc 6
2. Technical specifications
2.1 General Features:
Operating temperature
0÷40°C for higher temperature see derating curve
Voltage power supply
24V minimum, 480V max and 600V on request
Input signal
SSR
4÷20mA
0÷10V
potentiometer (10k ohm)
customer configurable with automatic zero/span calibration
Firing mode
One of these firing modes can be configured on line via serial port
Phase Angle + Current Limit (PA)
Soft Start + Phase Angle + Current Limit (S + PA)
Auxiliary voltage supply
230V ±15%; 10VA power consumption
440V ±15%; 10VA power consumption
Fan voltage supply
230V ±15%;
110V ±15%; on request
Heater break alarm
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors.
Latching alarm plus reset. Relay output 0,5A at 125V
Feedback
Voltage feedbak (V)
Square Voltage feedbak (V²)
Power feedback (VxI) (option)
Serial communication
RS485 Modbus protocol (option)
Mounting
Din rail mounting up to 45A
Bulk head over 45A
Protection IP20