Honeywell
CD3200 up to110A
User’s Manual ver. 2.0
www.honeywell.com/imc 42
10.3.7 Output Power
Parameter 5L
Command from controller
Operations:
Read
Meaning:
It rapresents a value in points (0-255, 0-FF Hex) and it’s the power demand in % of controller.
Example:
0%
= 0
0 (Hex)
50%
= 128
80 (Hex)
100%
= 255
FF (Hex)
Command via RS485
Operations:
Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex).
It’s power set point setted in thirst buffer.
Example:
0%
= 0
0 (Hex)
50%
= 128
80 (Hex)
100%
= 255
FF (Hex)
10.3.8 Output Power Ramping (0 – FFH)
Operations:
Read
10.3.9 Power adjust
Parameter 6
Operations:
Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex).
It’s a scaling factor of power demand.
Example 1:
0% = 0
50% =
128
100% = 255
Example 2:
•
Output Power: 100
Power Limit: 100%
-> Real power: 100
•
Output Power: 100
Power Limit: 50%
-> Real power: 50
•
Output Power: 80
Power Limit: 50%
-> Real power : 40
100
Power Adjust = 100%
Power Adjust = 80%
Power Adjust = 40%
80
60
40
20
0
40
20
60
100
80
Input %
OUT %