10.3.10 Current Limit
Parameter 7
Command from current limit pot.
Operations
: Read
Meaning:
It represents a value in points (0-255, 0-FF Hex) and it’s the power demand in % of controller.
Example:
0%
= 0
0 (Hex)
50%
= 128
80 (Hex)
100%
= 255
FF (Hex)
Command via RS485
Operations:
Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex)
It’s the power set point setted in thirst buffer
Example:
0%
= 0
0 (Hex)
50%
= 128
80 (Hex)
100%
= 255
FF (Hex)
10.3.11 Status Table
Bit Meaning
Notes
0
Short circuit on SCR
Read only
1
Load Failure
Read only
2 On-Off
Read
only
3
HB Calibration in progress
Read only 0=Normal - 1=Calibration
4
Current Limit Flag
Read only 0=Normal - 1= Working in C.L.
5 Termal
Read
only
10.3.12Short circuit on SCR
Bit 0
Operations:
Read
Meaning:
It’s a bit indicating when the thyristor is in short circuit.
0
= OK
1
= Short circuit
10.3.13 Load Failure
Bit 1
Operations:
Read
Meaning:
It’s a bit indicating the partial or total load failure.
0
= OK
1
= Load failure