11. Maintenance
11.1 Trouble Shooting
Small problems sometimes can be solved locally with the help of the below tab of trouble shooting.
If you don’t succeed, contact us or your nearest distributor.
Symptom Indication
on
front unit
Possible reasons of
the symptom
Actions
Green LED is
always light off.
-
No voltage auxiliary
power supply to
terminals 1-3 (see
wiring diagram).
-
Give auxiliary voltage supply
to terminals 1-3.
Green LED (PW)
light on and
green LED (ON)
in light off
condition.
-
No input signal.
-
Reversed polarities of
input signal.
-
Reset contact in open
condition (see wiring
diagram).
-
Provide to give input signal.
-
Reverse the input signal
polarity.
-
Make link on reset terminals.
Thyristor unit
doesn’t go in
conduction with
input signal.
Green LED (PW)
in light on
condition and
green LED (ON)
in light on
condition.
-
Fuse failure.
-
Load failure.
-
Load connection
interruption.
-
Thyristor faulty and
always in open
circuit.
-
With HB option the
yellow led (HB) in
light on condition.
-
Substitute the fuse.
-
Repair the load.
-
Provide to repair the wiring.
-
Substitute the faulty thyristor.
-
Check the load.
Load current
flows also with
no input signal.
Green LED (ON)
always in light
off condition.
-
Short circuit on
thyristor. If there is
HB circuit the red
LED (SC) is light on.
-
Substitute the thyristor. Check
that load is not in short
circuit.
Current flows at
nominal value
but yellow LED
(HB) in light on
condition.
Yellow HB in light
on condition.
-
HB circuit not tuned.
-
Current transformers
not properly wired (if
are external to
CD3200).
-
Push CAL button in front unit
to start HB calibration
procedure.
-
Control current transformers
wiring and Push CAL button in
front unit to start HB
calibration procedure.
R
ED
LED (SC)
IS LIGHTED ALSO
IF CURRENT IS AT
NOMINAL VALUE
.
Red LED in light
on condition.
-
HB circuit not
properly tuned.
-
Push CAL button in front unit
to start HB calibration
procedure.
Thyristor unit
doesn’t work
properly.
-
Wrong input signal
selection.
-
Wrong input signal
calibration (out of
range).
-
Auxiliary voltage
supply out of limits.
-
Control input signal setting.
-
Repeat input calibration
procedure.
-
Verify the auxiliary voltage
supply.