6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Programming
Section 9: Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses
these menu options in detail. All options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
9.1 UL 864 Programming Requirements
9.2 Modules
This section lists the options available under the module option in the program menu. The following modules are available for the con-
trol panel: 5860, 6860, 6855 LCD annunciators, 5824 serial/parallel printer interface module, 5496 NAC Expander or 5895XL power
supply, 5880 LED I/O module, and 5865 LED annunciator, SK-NIC Network Interface Card.
9.2.1 Edit Modules
The features that can be edited when this option is selected are, module name, and class of wiring (Class A or Class B).
To edit an existing module, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 1 to enter module menu.
4.
Press 1 to edit a module.
5.
Use the up or down arrow to select the module you wish to edit.
Editing Module ID
6.
Press the up or down arrow key to modify the module ID.
Naming Modules
You can assign an English name to a system hardware module to make it easier to recognize on a display.
7.
If you wish to edit the modules name press the up or down arrow to select each character for the modules name (or press the right
arrow to bypass name edit). Press the right arrow to move to the next character.
!
CAUTION:
Before any customized programming is done, JumpStart should be run first. After Jump-start is run, thoroughly test the
system. The reason the system should be tested after JumpStart is because JumpStart automatically programs the system, searching for and
configuring all SLC and SBUS devices it finds. Jump-start allows you to confirm the integrity of the installation prior to performing any
custom programming. After determining that the hardware is properly installed, custom programming can be performed. Refer to Section 6.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES:
This product incorporates field programmable software. In order for the product to comply with
the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to specific values or not used at all as indicated
below.
Programming Option
Menu Item
Permitted in
UL 864 (Y/N)
Possible
Settings
Settings
Permitted in
UL 864
Time Options
Auto-resound
Yes
4 hrs, 24 hrs
4 hours if using
SWIFT devices
Time Options
Low AC Report
Delay
Yes
0–30 hours
1–3
Display Oldest Event
Y (Enabled)
Yes
Yes & No
Yes
N (Disabled)
No
Yes & No
No
Alarm Verification
Alarm
Verification
Yes
60-250
(confirmation
period)
60
NOTE:
Internal devices and the SK-NIC are not able to have their module ID edited.
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......