130
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Reporting
Repeater Rx1 communication trou-
ble
EM
0101
EMNN000101
1
334
Panel ID
101
Repeater Rx1 communication trou-
ble restore
EN
0101
ENNN000101
3
334
Panel ID
101
Repeater Rx2 communication trou-
ble
EM
0102
EMNN000102
1
334
Panel ID
102
Repeater Rx2 communication trou-
ble restore
EN
0102
ENNN000102
3
334
Panel ID
102
SBUS Class A supervision lost
ET
Exp. ID
ETNNXX0000
1
333
Exp. ID
000
SBUS Class A supervision restore
ER
Exp. ID
ERNNXX0000
3
333
Exp. ID
000
SBUS expander trouble
ET
Exp. ID
ETNNXX0000
1
333
Exp. ID
000
SBUS expander trouble restore
ER
Exp. ID
ERNNXX0000
3
333
Exp. ID
000
SLC class A supervision trouble
ET
Exp. ID
ETNNXX0000
1
331
Exp. ID
000
SLC class A supervision trouble re-
store
ER
Exp. ID
ERNNXX0000
3
331
Exp. ID
000
SLC programming ended, system
active
TE
0
TENN000000
3
607
00
000
SLC programming started, system
shut down
TS
0
TSNN000000
1
607
00
000
SLC short circuit trouble
ET
Exp. ID
ETNNXX0000
1
332
Exp. ID
000
SLC short circuit trouble restore
ER
Exp. ID
ERNNXX0000
3
332
Exp. ID
000
Time changed event
JT
0
JTNN000000
1
625
00
000
Unable to report to account
trouble
RT
Receiver # RTNN00RRRR
1
354
00
Receiver
#
Unable to report to account
trouble restore
YK
Receiver # YKNN00RRRR
3
354
00
Receiver
#
User access code changed
JV
0
JVNN000000
1
602
00
000
User initiated manual dialer test
RX
0
RXNN000000
1
601
00
000
Walk test begin
TS
0
TSNN000000
1
607
00
000
Walk test end
TE
0
TENN000000
3
607
00
000
Zone Events
Zone events are reported only when “Report by Zone” is selected
Auxiliary power trouble
FT
0000
FTNN000000
1
320
00
000
Auxiliary power trouble restore
FJ
0000
FJNN000000
3
320
00
000
CO Detector Alarm
GA
Zone #
GANN000ZZZ
1
162
00
Zone #
CO Detector Alarm Restore
GH
Zone #
GHNN000ZZZ
3
162
00
Zone #
CO Detector Supervisory Alarm
GS
Zone #
GSNN000ZZZ
1
200
00
Zone #
CO Detector Supervisory Alarm Re-
store
GR
Zone #
GRNN000ZZZ
3
200
00
Zone #
CO Detector Trouble
GT
Zone #
GTNN000ZZZ
1
373
00
Zone #
CO Detector Trouble Restore
GJ
Zone #
GJNN000ZZZ
3
373
00
Zone #
Detector Alarm
FA
Zone #
FANN000ZZZ
1
110
00
Zone #
Detector Alarm Restore
FH
Zone #
FHNN000ZZZ
3
110
00
Zone #
Detector trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Detector trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
ECS Switch Trouble
QT
0
QTNN000000
1
242
00
000
ECS Switch Trouble Restore
QJ
0
QJNN000000
3
242
00
000
ECS Supervisory/Tamper Alarm
QS
0
QSNN000000
1
241
00
000
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 11.3 : Reporting Formats Table
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...