6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
111
Programming
8.
Enter the number of hours (0-30) before a low AC report will be sent to the central station, then press ENTER. Refer to Figure 9.10.
Figure 9.10 Low AC Report Delay Programming Screen
Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Internal. AC Frequency feature dictates how the control panel will calculate
time based on the AC line frequency used in the installation site. The “Internal” option can be used in areas where the AC line frequency
is not dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC
power source and either 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz. selection
To change the AC line frequency, continue programming from step 8 above:
9.
Select 50, 60 or Intl, by pressing the up or down arrow, then press ENTER.
Clock Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/Pm display format) or MIL (for military or 24 hr display format) by pressing the up or down arrow, then
press ENTER.
Auto-Resound (4 or 24 hours)
The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will
automatically resound events after being silenced. Set this option to 4 hours when using SWIFT devices
9.6.3 Miscellaneous Options
Through this programming option you can turn on or off strobe synchronization during silence, display status at idle (auto display event),
report by zone or point, Plexiglas door, and single key ack.
To edit Miscellaneous Options:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Misc. Options.
Synchronize Strobes Active During Silence
When “SYNC Strbs w/ Sil:” is Selected as Y (Yes) then strobes will continue to flash when the system is silenced and will stop flashing
when the system is reset.
5.
Press the up or down arrow to toggle this selection between Y (Yes) or N (No).
6.
Press the right arrow or ENTER to make your selection and move to the next programming option.
Auto Display Oldest Event
When this feature is programmed Y (Yes) then the oldest un-acknowledge event will automatically display on the control panel and
remote annunciators after there has been no activity on any system touchpad for two minutes.
7.
Press the up or down arrow to toggle this selection between Y (Yes) or N (No).
8.
Press the right arrow or ENTER to make your selection and move to the next programming option.
9.6.4 Daylight Savings Options
From Daylight Savings, you set the set the start and end week and month of Daylight Saving Time.
To edit Daylight Savings:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 6 for Daylight Savings.
Automatic Daylight Saving Time Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If this feature is not enabled (set to
No
), the Day-
light Saving Time change is not made to the system clock.
Low AC Report
Delay in Hours
(00 - 30)
NOTE:
The “SYNC Strbs w/ Sil:” only functions with outputs that use a synchronized output pattern.
NOTE:
See Section 9.4 for more information about Synchronization protocol choices
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......