6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
139
Reporting
For examples see Table 11.5.
Event
Report
Zo
ne
/
Panel ID
Module
MM
Z
one
ZZ
ZZ
Point
ZZ
ZZ
Fie
ld
s
Se
nt
SIA
Event
Data
Fire Alarm-Zone
Zone
32
n/a
15
n/a
EE-PP-MM-
ZZZZ
FA32000015
Fire Alarm-Zone
Zone
32
n/a
05
n/a
EE-PP-MM-ZZZZ
FA32000005
Fire Alarm-Point
Point
32
01
n/a
123
EE-PP-MM-ZZZZ
FA32010123
Fire Alarm-Point
Point
21
33
n/a
203
EE-PP-MM-ZZZZ
FA21330203
Expander Trouble
n/a
15
11
n/a
n/a
EE-PP-MM-ZZZZ
ET15110000
Auto Test
n/a
32
n/a
n/a
n/a
EE-PP-MM-ZZZZ
RP32000000
Battery Trouble-Panel 32
n/a
32
98
n/a
n/a
EE-PP-MM-ZZZZ
YT32980000
Battery Trouble-Expander 18
n/a
32
18
n/a
n/a
EE-PP-MM-ZZZZ
YT32180000
SLC Loop Shorted
n/a
01
44
n/a
n/a
EE-PP-MM-ZZZZ
ET01440000
Program Begin
n/a
32
n/a
n/a
n/a
EE-PP-MM-ZZZZ
LB32000000
Program Begin
n/a
22
n/a
n/a
n/a
EE-PP-MM-ZZZZ
LB22000000
AC Power Loss- Panel 22
n/a
22
98
n/a
n/a
EE-PP-MM-ZZZZ
AT22980000
MM = 00
Fire Trouble
Point
22
97
n/a
200
EE-PP-MM-ZZZZ
FT22970200
Fire Trouble
Zone
22
97
1
n/a
EE-PP-MM-ZZZZ
FT22970001
MM = 00
Fire Trouble-Nac
Point
22
98
n/a
Nac Circuit 7 EE-PP-MM-ZZZZ
FT22980007
ZZZZ=Pt. #
Fire Trouble-Nac
Zone
22
98
n/a
Nac Circuit 7 EE-PP-MM-ZZZZ
FT22980007
ZZZZ=OPG #
Table 11.5: SIA REPORTING EXAMPLES
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......