24
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
Before You Begin Installing
The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn from
the panel.
Use next size battery with capacity greater than required.
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA mA
Alarm: 145 mA
mA
5865-3 LED Annunciator
Standby: 35 mA mA
Alarm: 145 mA
mA
5880 LED I/O Module
Standby: 35 mA mA
Alarm: 200 mA
mA
5883 Relay Interface
(32 max.)
Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
5496 NAC Expander
(8 max.)
Standby/Alarm: 10 mA mA
mA
5895XL Power Supply
Standby/Alarm: 10 mA mA
mA
Network Cards
SK-NIC Network Interface Card
(1 Max.)
Standby/Alarm: 21 mA mA
mA
SK-FML Fiber Optic Multi Mode
(1 Max.)
Standby/Alarm: 53 mA mA
mA
SK-FSL Fiber Optic Single Mode
(1 Max.)
Standby/Alarm: 79 mA mA
mA
A
Total System Current
Auxiliary Devices
3
Refer to devices manual for current rating.
IPDACT-2 IP Communicator
Alarm: 136 mA
mA
Standby: 93 mA mA
IPDACT-2UD IP Communicator
Alarm: 155 mA
mA
Standby: 98 mA mA
CELL-MOD/CELL-CAB-SK
Standby: 55 mA mA
Alarm: 100 mA
mA
Alarm/Standby: mA mA
mA
Alarm/Standby: mA mA
mA
Alarm/Standby: mA mA
mA
B
Auxiliary Devices Current
Notification Appliance Circuits
Refer to devices manual for current rating.
5495/5499 Power Supply
24 VDC
One input circuit: 15 mA
mA
Both input circuits: 30 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA
mA
E
Total current ratings converted to amperes (line D x .001):
A
A
F
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
H
G
Multiply lines E and F.
Total standby AH
AH
H
Alarm sounding period in hours. (For example, 5 minutes =.0833 hours)
H
I
Multiply lines E and H.
Total alarm AH
AH
J
Add lines G and I.
4
AH
Multiply by the Derating Factor
x 1.25
Total ampere hours
required
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.3 Current Draw worksheet for SD Devices
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......