Agency Listings, Approvals, and Requirements
2.
Use the addressable smoke detectors specified in Section 7 of this manual and or conventional detectors listed in the compatibility
chart. (See Appendix A.)
3.
Use UL listed notification appliances compatible with the 6808 from those specified in the Appendix A at the back of this manual.
4.
A full system checkout must be performed any time the panel is programmed.
Restricted Options:
•
The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 3 hours. For UL certified installations this
number must be set from 1 to 3 hours.
•
The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications
whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
•
The system allows the Alarm Verification time to be set from 60 to 250 seconds. For UL certified installations the setting must be a
minimum of 60 seconds.
•
The system allows the Auto-resound time to be set to 24 or 4 hours. For UL certified installations that are utilizing SWIFT devices,
the value must be set to 4 hours
•
Call forwarding shall not be used.
•
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature, and no delay shall be
used.
•
P.A.S feature shall be used only with automatic detectors.
2.2.2 Requirements for Central Station Fire Alarm Systems
1.
Use both phone lines. Enable phone line monitors for both lines.
2.
You must program a phone number and a test time so that the 6808 shall automatically initiate and complete a test signal
transmission sequence to its associated receiver at least once every 6 hrs.
3.
The AC Loss Hours option must be set from 1-3 hours.
4.
If using wired Ethernet or cellular, you must program the corresponding account/subscriber ID and a test time so that the FACP
shall automatically initiate a test signal transmission sequence to its associated receiver at least every 6 hrs.
2.2.3 Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used. Minimum system requirements are one Silent Knight addressable
initiating device.
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems
Minimum system requirements are one Honeywell Silent Knight addressable initiating device and either a 5220, Keltron 3158 or the
built-in Digital Alarm Communicator Transmitter (DACT).
1.
Do not exceed the current load restrictions shown in Section 3.7.2.
2.
The AC Loss Hours option must be set from 1-3 hours.
2.2.5 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
2.2.6 NFPA Requirements
The following is the minimum configuration to meet the NFPA requirements.
Model/Module
Description
Local
Releasing
Remote
Station
Auxiliary
Central
Station
Emergency
Signaling
006808CB
Enclosure
Y
Y
Y
Y
Y
Y
068080
Motherboard
Y
Y
Y
Y
Y
Y
RA-100BD
4 x20 display
Y
Y
Y
Y
Y
Y
SK-NIC
Network card
O
O
O
O
O
O
SK-FML/ -FSL
Fiber module
O
O
O
O
O
O
7644
Pol Rev device
N
N
Y
N
N
N
5220
City tie, Pol. Rev
Device
N
N
Y
Y
N
N
Keltron 3158
Rev Pol Module
N
N
Y
Y
N
N
Cell-Mod/Cell-Cab-
SK
Cellular
transmitter
N
N
Y
N
Y
N
Y = YES, N = NO, O = OPTIONAL
Table 2.2
NFPA Requirements for 6808
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......