Before You Begin Installing
* Regulated/special application when used for releasing.
3.5 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms.
To avoid induced noise, follow these guidelines:
•
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for the entire panel. Instead,
separate the wiring as follows:
•
Do not pull wires from different groups through the same conduit. If you must run them together, do so for as short a distance as
possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages separately.
•
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3.1 for an example.
Terminal Block 5
AC INPUT
B
AC input (hot)
120 VAC, 60 Hz
3.3 A
Earth
Earth Ground
N/A
N/A
W
AC input (neutral)
120 VAC, 60 Hz
3.3 A
Terminal Block 6
TROUBLE
NC
Normally closed relay contact
24 VDC
2.5 A, resistive
COM
Common terminal
NO
Normally open relay contact
RELAY 1
NC
Normally closed relay contact
24 VDC
2.5 A, resistive
COM
Common terminal
NO
Normally open relay contact
RELAY 2
NC
Normally closed relay contact
24 VDC
2.5 A, resistive
COM
Common terminal
NO
Normally open relay contact
NAC1*
–
Notification Appliance
Circuit/Auxiliary power
24 VDC
3.0 Amp NAC or Aux
power
+
NAC2*
–
Notification Appliance
Circuit/Auxiliary power
24 VDC
3.0 Amp NAC or Aux
power
+
NAC3*
–
Notification Appliance
Circuit/Auxiliary power
24 VDC
3.0 Amp NAC or Aux
power
+
NAC4*
–
Notification Appliance
Circuit/Auxiliary power
24 VDC
3.0 Amp NAC or Aux
power
+
P8
EXT. Comm
Cellular
Connection
B
Cellular Transmitter
input
A
S+
55 mA, 95 mA
S-
P10
Data Network
Used for SK-NIC
24 VDC
21 mA
Terminal No.
Label
Description
Rating
Group
Individual
Voltage
Current
Table 3.1 Terminal Descriptions and Electrical Specifications
High voltage
AC power terminal
SLC loops
SLC In/Out Terminals
POTS reporting
input/output
Phone line circuits, Ring Tip Telco, Phone
Terminals
Notification circuits
NAC 1-4
SBUS SBUS
Out
Terminals,
Cellular communication
Relay circuits
Trouble, Relay 1, Relay 2 Terminals
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......