![Hochiki FireNET FN-DAC Installation And Operation Manual Download Page 62](http://html1.mh-extra.com/html/hochiki/firenet-fn-dac/firenet-fn-dac_installation-and-operation-manual_2143426062.webp)
62
FireNET FN-DAC Digital Alarm Communicator I & O Manual - v 1.0
Panel and Network Events
SIA Event
Code
Contact ID
Event Code
Test Zones
FI / FK
607
Test Zone Feature Activated
Tested Zone
TS / TE
604
Device Tested while 'Test Zones' Active
Trouble Routing Trouble
FT / FJ
320
Trouble on Trouble Routing Output
Unexpected Network Node
ET
330
Unexpected Panel Added to Network
Unexpected Peripheral
ET / ER
330
Unexpected Serial Device Added to
Panel
Loop Device Events
Event Generated By
Fire
FA / FH
110
FRCME, ATG, ALG, ALG-DH, AIE,
DIMM, CZM, AMS
1
Waterflow (Fire)
SA / SH
113
FRCME, DIMM
Waterflow (Supervisory)
FS / FV
200
FRCME, DIMM
Action = Trouble
FT / FJ
373
FRCME, DIMM, CZM
1
Action = Pre-Alarm
UA / UR
118
FRCME, DIMM, CZM, ATG, ALG, AIE,
ALG-DH
1
Action = Supervisory
SS / SR
203
FRCME, DIMM, CZM
1
Action = Supervisory
SS / SR
200
ATG, ALG, AIE, ALG-DH, AMS
Action = Auxiliary
UA / UH
140
FRCME, DIMM, CZM
1
Action = Silence
FL / FL
406
FRCME, DIMM, CZM
1
Action = Reset
OR / OR
313
FRCME, DIMM, CZM
1
Supervised Loop Trouble
FT / FJ
373
FRCME, DIMM, CZM, SOM
Input Trouble (Waterflow and
General Supervision)
ST / SJ
373
FRCME
Missing Device
FY / FJ
373
FRCME, SOM, R2M, DIMM, CZM, ASB,
AMS
Missing Sensor
FY / FJ
380
ALG, AIE, ATG, ALG-DH
Wrong Device Type / Bad
Data Trouble
FT / FJ
380
All Modules and Sensors
Double Address
FT / FJ
373
All Modules and Sensors
2
Unexpected Device
XE / FJ
373
All Modules and Sensors
2
Maintenance Trouble
FT / FJ
393
ALG, ALG-DH, AIE
Internal Trouble
FT / FJ
380
ALG, ALG-DH, AIE
No Auxiliary Power
FT / FJ
373
CZM, ASB
Ground Fault
YP / YQ
310
CZM
Note #1 – This event can also be generated by Panel and I/O Module Inputs.
Note #2 – Zone information is not reported for this event.
Note #3 – In SIA format, the following events use the same code for the activation and restore: Alarm
Silence (FL / FL) and Panel Reset (OR / OR).