50
FireNET FN-DAC Digital Alarm Communicator I & O Manual - v 1.0
Section 5 – Testing, Troubleshooting and Maintenance
After the FN-DAC installation and programming are complete, the system must be
tested for proper operation.
NOTE:
Follow NFPA testing methods and frequencies as outlined in the National Fire
Alarm Code (NFPA 72).
The FN-DAC communicator will report all panel and network events to the monitoring
station, based on network interface configuration and programming of the report
groups. When there is an event to be reported, the FN-DAC will seize the phone line,
dial the programmed number, report the event(s), and then disconnect. Events are
reported by priority, with Fire and Waterflow events being reported first. Note that at
times, more than one call may be generated to report an event or series of events.
To test the system, generate an event on the FireNET panel or network. Each event
will be reported, based on programming of the FN-DAC. Confirm receipt of all reports
with your monitoring station.
Troubleshooting –
Comms Phone Line 1 (or 2) Trouble
– The indicated phone line is not being detected
by the communicator.
•
Use a voltmeter to check the voltage on the phone line. A normal phone line
will measure approximately 48 VDC.
Caution
: The voltage present during ringing for an incoming call can be over 100
volts AC. Use caution when measuring phone line voltages.
•
Check to be sure that the incoming phone line is correctly connected to the
L1T and L1R (or L2T and L2R) line connections. See Figure 2.2.4.
•
Check wiring of the RJ31X jack(s). Be sure that the FN-DAC is connected
for proper line seizure.
Comms Fail #
- The communicator is unable to report to the monitoring station
receiver. The number indicates the account that failed.
•
Confirm that the monitoring station telephone number is correct in the
program.
•
Verify that the correct communication format is selected (Contact ID or SIA).
firealarmresources.com