FireNET FN-DAC Digital Alarm Communicator I & O Manual - v 1.0
Panel and Network Events
SIA Event
Code
Contact ID
Event Code
AC Fail
AT / AR
301
No AC to Panel
Alarm Silence
FL / FL
406
Alarm Silence Button Pressed
Aux Power Trouble
YP / YQ
312
Short or other Trouble on Aux Power
Battery Low
YT / YR
302
Low Battery
Battery Missing
YM / YR
311
Missing/Disconnected Battery
Comm Fail
YC / YK
354
Dialer Communication Failure
Dialer Missing
IA / IR
350
Dialer Ribbon Cable Unplugged
Disable Address
FB / FU
571
Address Disabled at Panel
Disable Audibles
FT / FJ
520
Notification Appliances Disabled
Disable Loop
FB / FU
571
Loop Disabled
Disable Zone
FB / FU
570
Zone Disabled
Disable Panel Output
FT / FJ
520
Panel Output Disabled
Disable Panel Input
UB / UU
520
Panel Input Disabled
Disable Printer
VZ / VY
336
Panel Printer Disabled
Disable Buzzer
FT / FJ
520
Panel Buzzer Disabled
Disable Ground Trouble
FT / FJ
520
Ground Fault Detection Disabled
Fire Drill
FI / FK
604
Fire Drill Button Pressed on Panel
Fire Routing Trouble
FT / FJ
320
Trouble on Fire Routing Circuit on Panel
Ground Fault
YP / YQ
310
Ground on External Panel Wiring
Loop Explorer Prog
LB
628
Local Programming with Loop Explorer
Loop Explorer Reset
FT / FJ
305
Panel Reset after Programming
Missing Network Node
ET / ER
330
Missing FireNET Panel on Network
Missing Peripheral
ET / ER
330
Missing Serial Device
NAC Trouble
FT / FJ
320
Trouble on Notification Appliance Circuit
Network Open/Short
NT / NR
330
Open or Short on Network Connection
Panel Reset (SW2)
FT / FJ
305
SW2 Button on Display Board Pressed
Panel Reset Button
OR / OR
313
Reset Button on Panel Pressed
Phone Line 1 Trouble
LT / LR
351
Trouble on Dialer Phone Line # 1
Phone Line 2 Trouble
LT / LR
352
Trouble on Dialer Phone Line #2
Prog Output Trouble
FT / FJ
320
Trouble on Prog Output on Panel
SLC Open Circuit
ET / ER
331
Open Circuit on Device Polling Loop
SLC Short Circuit
ET / ER
332
Short Circuit on Device Polling Loop
Test Report - Normal
RP
602
Normal Test Report
Test Report - Off Normal
RY
608
Off-Normal Test Report