26
FireNET FN-DAC Digital Alarm Communicator I & O Manual - v 1.0
Alarms –
•
Fire
Alarm
•
Waterflow
Alarm
•
Fire
Drill
Alarm Restore –
•
Fire Alarm Restore
•
Waterflow Alarm Restore
•
Fire Drill Restore
Supervisory, Trouble, Enable/Disable –
•
Supervisory (Activation and Restore)
•
All Trouble Conditions (Activation and Restore)
•
Pre-Alarm (Activation and Restore)
•
Auxiliary
(Activation and Restore)
•
Smoke Detector Maintenance Trouble (Activation and Restore)
•
Disable and Enable Events
•
Loop Explorer Programming Event (local and remote)
Service / Test –
•
“Test
Zones”
•
Device
Tested
•
Test
Report
System Reset –
•
Alarm Silence Event
•
Reset
Event
Backup Report
(Account 2 and 4 Only)
•
Account 2 and 4 can be selected to report to the associated phone number
as a
backup
of the primary account. For this feature, account 1 is
considered the primary account, with account 2 being its backup. Account 3
serves as a second primary, or duplicate account, with account 4 being its
backup.
If communication is not established to the primary account after the first five attempts,
the backup account will be used. Please see section 2.5.1 for additional details.
By default, all report groups are selected for each account. If it is necessary to change
the groups selected for a particular account you must use Loop Explorer. Please see
section 3.2 of this manual for details on programming with Loop Explorer.