4.1.2.2 Connection Method 2
1) Connection method 2 may be used as an alternative to method 1 at any time.
To begin, create a new project in Loop Explorer.
2) Add a panel to the site. It is important that the panel added be the same type
and same address as the panel that the FN-DAC is installed in at the jobsite (2-
loop panel, 4-loop panel or network annunciator).
3) Select the panel in the Navigator tree and add a Dialer to the panel. Do this by
double-clicking on the dialer icon in the Items pane.