4) Connect the telephone lines to the communicator. The communicator must be
connected upstream of any private telephone system at the protected premise.
See Figure 2.2.5.
Figure 2.2.5 – Telephone Connections
NOTE
: 26 AWG wire must be used between the RJ31X jacks and the FN-DAC
terminal block. DO NOT USE WIRE OTHER THAN 26 AWG.
NOTE
: To ensure proper connection to the Public Switched Telephone Network,
RJ31X jacks must be installed. UL Listed RJ31X jacks and cords must be used.
NOTE
: The maximum distance between the FN-DAC and RJ31X jacks must not
exceed 6 feet. Do not use a phone cord that is longer than 6 feet.
NOTE
: Two separate phone lines are required. Do not connect both telephone
interfaces on the FN-DAC to the same telephone line.