URRENT OUTPUT
If in
P01 a=0
, this programming step is irrelevant.
If level, level percentage, volume or volume percentage should be measured (a
•0 in
P01
) as well as first and last data pair of the linearisation
table have been entered then in the procedure of the data handling the minimum and maximum values (level or volume) are in engineering units
available.
Since current outputs should be assigned to these values in parameters
P10
and
P11
are the level and volume values entered.
P10: Assignment of 4 mA to the minimum level, level percentage, volume or volume percentage.
P11: Assignment of 20 mA to the maximum level, level percentage, volume or volume percentage.
DEFAULT:
P10
: 0
P11
: 9999
P12: - - - a “Error” indication by the current output
“Error” condition will be indicated by the current output. This indication below is on as long as the error lasts.
a
“Error” indication
1
3.8 mA
2
22 mA
DEFAULT: 2