TÜV-A 03 ATEX 0019X
♦
cbr2052a0600p_01
♦
36/21
Screen
Actions
öµ÷
øøø§ø
Assignment of 20 mA to the maximum level , %
Fill the tank to the level required. After entering the Quickset programming mode the learning function can be started
with the double key pressing + . During learning the image „Store” then 100% is displayed.
The parameter value represents degree in %. “Indirect” assigment of 20 mA to the maximum level with partially filled
tank: Following learning enter the momentary % value of level with the buttons. The output current will be set in
accordance % value.
ùfú>û
ü§üüü
“Error indication” by the output current
Pressing or either of two outputs can be selected: Indication of “3,8” or “22” should apply for 3,8 or 22 mA current
output
DEFAULT 22 mA
ýþ
ÿ
Damping
– To select damping keys / should be used
DEFAULT 10 sec
Note: – Current output can also be programmed for inverted operation: 4 mA = 100% (Full), 20 mA = 0% (Empty)
– Programming partially filled tank see under 5.1
– Description of failures can be found under 7 Error Codes.