28/36
♦
TÜV-A 03 ATEX 0019X
♦
cbr2052a0600p_01
6.3. M
EASUREMENT OPTIMALISATION
P20: - - - a Damping
This parameter can be used to reduce unwanted fluctuation of the display and output.
a
Damping (sec)
Remark
0
No damping
1
3
Applicable
2
6
Recommended
3
10
Recommended
4
30
Recommended
5
60
Recommended
6
100
Applicable
7
300
Applicable
DEFAULT: 10 sec
P32: Density of the medium (kg/dm
3
or lb/ft
3
in accordance with setting of (c) in P00)
If entering value other than 0 weight will be displayed (in
kg/dm
3
or lb/ft
3
in accordance with setting of (c) in
P00
and (b) in
P02
) instead of volume
DEFAULT: 0